![Rockwell Automation Allen-Bradley PanelView Plus 400 User Manual Download Page 153](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-panelview-plus-400/allen-bradley-panelview-plus-400_user-manual_1475651153.webp)
Publication 2711P-UM001D-EN-P - September 2005
Transfer files and Upgrade Firmware
7-5
3.
If other terminals exist on the same Ethernet network, the
following error may display:
"Error registering name on network (may be duplicate). Change
in system Control Panel and try again."
Ignore this error. It will be corrected during the upgrade. Press
OK
to acknowledge error and wait for terminal to reset.
4.
On touch or touch/screen terminals, you must calibrate the
touch screen by selecting pointers in all four corners of the
screen and pressing the middle of the screen when prompted.
5.
Ignore the following message if it appears. It means RSView ME
is being installed. Do not touch the two buttons that appear with
this message.
"Machine edition may be corrupted. Do you want to download
firmware?"
6.
When the upgrade is complete, a dialog appears requesting you
to remove the compact flash card from the card slot. Remove the
card and press F8 or Exit to reset the terminal.
7.
Communication settings are cleared when the terminal is
upgraded. If Ethernet communications is used, reconfigure the
Ethernet communication settings using the values recorded
when preparing the terminal.
8.
Replace the .MER files that you backed up before starting the
upgrade or download a new .MER file to the terminal.
9.
Load the .MER file and run the project.
TIP
If a USB mouse is available you can
acknowledge this error by selecting OK.
TIP
You can configure your application to start
automatically on power cycle under Startup
Options.
Summary of Contents for Allen-Bradley PanelView Plus 400
Page 1: ...PanelView Plus Terminals 2711P 400 600 700 1000 1250 1500 User Manual...
Page 6: ...Publication 2711P UM001D EN P September 2005 Table of Contents iv...
Page 44: ...Publication 2711P UM001D EN P September 2005 2 16 Installation...
Page 56: ...Publication 2711P UM001D EN P September 2005 3 12 Connect Power...
Page 160: ...Publication 2711P UM001D EN P September 2005 7 12 Transfer files and Upgrade Firmware...
Page 176: ...Publication 2711P UM001D EN P September 2005 8 16 Troubleshooting...
Page 182: ...Publication 2711P UM001D EN P September 2005 B 2 Compatible USB Devices...
Page 191: ...Publication 2711P UM001D EN P September 2005 Index 5...
Page 192: ......