Publication 2711P-UM001D-EN-P - September 2005
Terminal Connections
6-17
Remote I/O Connections
Use the Belden 9463 twin axial or equivalent cable (cat. no. 1770-CD),
to connect a terminal to a Remote I/O scanner. The maximum cable
length (link distance) is determined by the baud rate.
•
2,800 m (10,000 ft) for 57.6K baud
•
1,400 m (5,000 ft) for 115.2K baud
•
700 m (2,500 ft) for 230.4K
See Programmable Controller Wiring and Grounding Guidelines,
Publication 1770-4.1. The user manual for the I/O scanner module
also provides cabling information.
PanelView Plus 400-1500
Remote I/O Port on Communication Module
•
82
Ω
terminating resistor for 230.4K
bits/sec
•
150
Ω
terminating resistor for 57.6K
and 115.2K bits/sec
Blue 3
Shield SH 2
Clear 1
Belden
To Controller
Terminating Resistor
Summary of Contents for Allen-Bradley PanelView Plus 400
Page 1: ...PanelView Plus Terminals 2711P 400 600 700 1000 1250 1500 User Manual...
Page 6: ...Publication 2711P UM001D EN P September 2005 Table of Contents iv...
Page 44: ...Publication 2711P UM001D EN P September 2005 2 16 Installation...
Page 56: ...Publication 2711P UM001D EN P September 2005 3 12 Connect Power...
Page 160: ...Publication 2711P UM001D EN P September 2005 7 12 Transfer files and Upgrade Firmware...
Page 176: ...Publication 2711P UM001D EN P September 2005 8 16 Troubleshooting...
Page 182: ...Publication 2711P UM001D EN P September 2005 B 2 Compatible USB Devices...
Page 191: ...Publication 2711P UM001D EN P September 2005 Index 5...
Page 192: ......