Publication 2711P-UM001D-EN-P - September 2005
Terminal Connections
6-13
DH+ Status Indicator
DH-485 Status Indicator
Remote I/O Scanner Mode Status Indicator
Condition
Indication
off
Channel is not online
blinking green
Device is only node on the network.
solid green
Device is online and receiving token.
blinking red
Duplicate node
solid red
Failed selftest
Condition
Indication
off
Channel is not online
blinking green
Device is only node on the network.
solid green
Device is online and receiving token.
blinking red
Parity error
solid red
Failed selftest
Condition
Indication
off
Channel is not online
blinking green
At least one but not all adapters in
the scanlist are not responding.
solid green
All adapters in the scanlist are
responding.
blinking red
None of the adapters in the scanlist
are responding.
solid red
Failed selftest
Summary of Contents for Allen-Bradley PanelView Plus 400
Page 1: ...PanelView Plus Terminals 2711P 400 600 700 1000 1250 1500 User Manual...
Page 6: ...Publication 2711P UM001D EN P September 2005 Table of Contents iv...
Page 44: ...Publication 2711P UM001D EN P September 2005 2 16 Installation...
Page 56: ...Publication 2711P UM001D EN P September 2005 3 12 Connect Power...
Page 160: ...Publication 2711P UM001D EN P September 2005 7 12 Transfer files and Upgrade Firmware...
Page 176: ...Publication 2711P UM001D EN P September 2005 8 16 Troubleshooting...
Page 182: ...Publication 2711P UM001D EN P September 2005 B 2 Compatible USB Devices...
Page 191: ...Publication 2711P UM001D EN P September 2005 Index 5...
Page 192: ......