Module Tags
Appendix A
Input Tags
Table 30 - Modbus Slave Input Tags
Name
Data Type
Definition
Valid Values
I
x
.RunMode
BOOL
Channel’s operating state
• 0 = Idle
• 1 = Run
I
x
.ConnectionFaulted
BOOL
Indicates if a connection is running.
The module sets this tag to 0 when connected. If the module is not
connected, it changes the tag to 1.
• 0 = Connection running
• 1 = Connection not running
I
x
.DiagnosticActive
BOOL
Indicates if any diagnostics are active or if the prognostics threshold is
reached.
• 0 = No diagnostics active
• 1 = One or more diagnostics are active or the
prognostics threshold is reached
I
x
.DiagnosticSequenceCount
SINT
Increments for each time a distinct diagnostic condition is detected,
and when a distinct diagnostic condition transitions from detected to
not detected.
Set to zero by product reset or power cycle. Wraps from 255 (-1) to 1
skipping zero.
-128…+127
The value of 0 is skipped except during module
power-up.
I
x
.Slave.Fault
BOOL
Indicates that channel data is inaccurate and cannot be trusted for use in
the application.
• 0 = Good
• 1 = Bad, causing fault
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT
: Once the condition that causes
the tag to change to 1 is removed, the tag
automatically resets to 0.
I
x
.Slave.Uncertain
BOOL
Indicates that the channel data can be inaccurate but the degree of
inaccuracy is not known.
• 0 = Good data
• 1 = Uncertain data
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT
: Once the condition that causes
the tag to change to 1 is removed, the tag
automatically resets to 0.
I
x
.Slave.CRC_LRCError
BOOL
Status shows that CRC (LRC) Error is occurred or not
• 0 = Non-occurrence
• 1 = Occurrence
I
x
.Slave.ParityError
BOOL
Status that shows whether a parity error has occurred or not.
• 0 = Non-occurrence
• 1 = Occurrence
I
x
.Slave.IllegalDataAddress
BOOL
Status shows that user requests out of Modbus Register Address
• 0 = Non-occurrence
• 1 = Occurrence
I
x
.Slave.BufferOverrun
BOOL
Status shows that whether Over Run is occurred or not in ASIC.
• 0 = Non-occurrence
• 1 = Occurrence
I
x
.Slave.FramingError
BOOL
Shows if there was a framing error.
• 0 = Non-occurrence
• 1 = Occurrence
I
x
.Slave.SequenceNumberAck
INT
Acknowledges the sequence number.
• -32768…+32767
I
x
.Slave.MasterUpdateCount
INT
Any Modbus change will update this counter.
• -32768…+32767
I
x
.Slave.HoldingRegister[x]
(1)
INT
Produce Data that are written by Modbus Master as Data in Produce Tag.
• -32768…+32767
I
x
.Slave.Coil[x]
(2)
SINT
Produce Data that are written by Modbus Master as Data in Produce Tag.
• -128…+127
(1) X represents any possible value 0…99
(2) X represents any possible value 0…15