128
Rockwell Automation Publication 5069-UM003B-EN-P - January 2020
Appendix A
Module Tags
Channel Configured for
DF1—Radio Modem
This screen capture shows the tags that are described in the following tables.
Input Tags
Output Tags
Table 37 - DF1 Radio Modem Input Tags
Name
Data Type
Definition
Valid Values
I
x
.DF1.RunMode
BOOL
Channel’s operating state
• 0 = Idle
• 1 = Run
I
x
.DF1.ConnectionFaulted
BOOL
Indicates if a connection is running.
The module sets this tag to 0 when connected. If the module is not
connected, it changes the tag to 1.
• 0 = Connection running
• 1 = Connection not running
I
x
.DF1.DiagnosticActive
BOOL
Indicates if any diagnostics are active or if the prognostics threshold
is reached.
• 0 = No diagnostics active
• 1 = One or more diagnostics are active or the
prognostics threshold is reached
I
x
.DF1.DiagnosticSequenceCount
SINT
Increments for each time a distinct diagnostic condition is detected,
and when a distinct diagnostic condition transitions from detected
to not detected.
Set to zero by product reset or power cycle. Wraps from 255 (-1) to 1
skipping zero.
• -128…+127
The value of 0 is skipped except during module
power-up.
I
x
.DF1.CTS
BOOL
Indicates whether the CTS is active.
• 0 = Inactive
• 1 = Active
I
x
.DF1.RTS
BOOL
Indicates whether the RTS is active.
• 0 = Inactive
• 1 = Active
I
x
.DF1.DSR
BOOL
Indicates whether the DSR is active.
• 0 = Inactive
• 1 = Active
I
x
.DF1.DCD
BOOL
Indicates whether the DCD is active.
• 0 = Inactive
• 1 = Active
I
x
.DF1.DTR
BOOL
Indicates whether the DTR is active.
• 0 = Inactive
• 1 = Active
I
x
.DF1.MsgProcessing
BOOL
Determine if instruction message is processing.
• 0 = Not Processing
• 1 = Processing
Table 38 - DF1 Radio Modem Output Tags
Name
Data Type
Definition
Valid Values
O
x
.DF1RadioModem.StoreAndForward
INT (16)
Defines the stations that need to be involved in the Store and Forward function.
• 0 = Inactive
• 1 = Active