Rockwell Automation Publication 2198-UM001D-EN-P - May 2014
35
Planning the Kinetix 5500 Drive System Installation
Chapter 2
Table 14 - Power Dissipation Specifications
Minimum Clearance Requirements
This section provides information to assist you in sizing your cabinet and
positioning your Kinetix 5500 drive:
•
Additional clearance is required for cables and wires or the shared-bus
connection system connected to the top of the drive.
•
Additional clearance is required if other devices are installed above and/or
below the drive and have clearance requirements of their own.
•
Additional clearance left and right of the drive is required when mounted
adjacent to noise sensitive equipment or clean wire ways.
•
The recommended minimum cabinet depth is 300 mm (11.81 in.).
Figure 12 - Minimum Clearance Requirements
Kinetix 5500 Drive
Cat. No.
Frame
Size
Usage as % of Rated Power Output
(watts)
20%
40%
60%
80%
100%
2198-H003-ERS
x
1
12
25
37
50
62
2198-H008-ERS
x
2198-H015-ERS
x
2
40
80
120
160
200
2198-H025-ERS
x
2198-H040-ERS
x
2198-H070-ERS
x
3
64
128
192
256
320
Clearance right of the
drive is not required.
Clearance left of the
drive is not required.
Kinetix 5500
Servo Drive
40 mm (1.57 in.) clearance below
drive for airflow and installation.
40 mm (1.57 in.) clearance above
drive for airflow and installation.
Refer to the Kinetix Servo Drives
Technical Data, publication
for Kinetix 5500 drive dimensions.
IMPORTANT
Mount the drive in an upright position as shown. Do not mount the drive on its side.