122
Rockwell Automation Publication 750-TG101A-EN-P - June 2022
Chapter 5 Frame 6 Renewal Kits Installation
11. Remove the M6 hexagonal nuts from the DC bus bar terminals.
12. Loosen the two M4 x 8 mm slotted-Torx screws that secure the upper
chassis bracket to the chassis and remove the bracket.
13. Remove the two M4 x 8 mm slotted-Torx screws that secure the lower
stirring fan assembly to the chassis.
14. Lift the bus capacitor cover, upper support bracket, and lower stirring
fan assembly off the drive.
IMPORTANT
An edge connector on the main control circuit board in the control
pod is connected to the power interface circuit board below with a
ribbon cable. The ribbon cable fits through an opening in the back of
the control pod chassis.
12
M4 x 8 mm
T20 or F - 6.4 mm (0.25 in.)
2.6 N
•
m (23.0 lb
•
in)
11
M6
10 mm
5.2 N
•
m (46.0 lb
•
in)
13
M4 x 8 mm
T20 or F - 6.4 mm (0.25 in.)
2.6 N
•
m (23.0 lb
•
in)
Loosen Only. Shown Removed for Clarity Only.