SECTION 8: V
ENTING
51
8.13 Vertical Venting (Category I) 4" (10 cm) Pipe
NOTE:
It is not required for the contractor to perform a leak test for vertical venting (Category I)
configurations.
Vent Cap
24”
Minimum
Storm Collar
Roof Flashing
Tee Fitting or Alternative Elbow
Clean Out Cap
Heater
Roof
Double-Wall
Type-B Vent
4" (10 cm)
Single Wall Pipe (Type-C)
or Double Wall (Type-B) Vent
When using type-B vent on
horizontal section, use B to
C adapter (supplied by others)
and attach to end of tube in
place of supplied vent adapter.
Note:
With the exception of the
Metalbestos vent cap, all vent
material is supplied by others.
Description
Part Number
Vent Cap, Metalbestos - 4" (10 cm)
90502300
Summary of Contents for VANTAGE HEV-100