HEV-S
ERIES
I
NSTALLATION
, O
PERATION
AND
S
ERVICE
M
ANUAL
6
NOTE:
1. All dimensions are from the surfaces of all tubes, couplings and elbows.
2. Clearances B, C and D can be reduced by 50% after 25' (7.5 m) of tubing downstream
from where the burner and burner tube connect.
FIGURE 5: LEVEL SIDE REFLECTOR
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
HEV-40
6
9
53
44
16
23
135
112
HEV-60
6
9
63
47
16
23
161
120
HEV-80
6
9
70
54
16
23
178
138
HEV-100
6
9
77
59
16
23
196
150
HEV-125
6
9
83
65
16
23
211
166
HEV-150
6
9
86
69
16
23
219
176
HEV-175
8
9
88
73
21
23
224
186
A
C
D
B
FIGURE 6: TWO SIDE REFLECTORS
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
HEV-40
6
15
53
15
16
39
135
39
HEV-60
6
23
66
23
16
59
168
59
HEV-80
6
25
72
25
16
64
183
64
HEV-100
6
27
78
27
16
69
199
69
HEV-125
6
32
84
32
16
82
214
82
HEV-150
6
35
88
35
16
89
224
89
HEV-175
8
40
91
40
21
102
232
102
A
C
D
B
FIGURE 7: 45
°
TILT REFLECTOR
(inches)
(centimeters)
Model
A
B
C
D
A
B
C
D
HEV-40
8
8
51
46
21
21
130
117
HEV-60
8
8
60
54
21
21
153
138
HEV-80
8
8
66
60
21
21
168
153
HEV-100
10
8
74
64
26
21
188
163
HEV-125
10
8
78
69
26
21
199
176
HEV-150
12
8
84
74
31
21
214
188
HEV-175
12
8
85
79
31
21
216
201
Summary of Contents for VANTAGE HEV-100
Page 2: ......
Page 4: ......
Page 25: ...SECTION 6 HEATER INSTALLATION 21 FIGURE 20 Linear Heater Layout Overview Continued ...
Page 41: ...SECTION 7 OPTIONAL HEATER ACCESSORIES 37 FIGURE 30 U Tube Heater Layout Overview Continued ...
Page 72: ...HEV SERIES INSTALLATION OPERATION AND SERVICE MANUAL 68 ...
Page 73: ...SECTION12 TROUBLESHOOTING 69 12 2 Manifold Gas Pressure Setting Side View of Heater ...
Page 78: ......
Page 79: ...2020 ...
Page 80: ......