SPECIFICATIONS
Technical:
Insulation: Class2, Double insulation.
Overvoltage category: CATIV 600V,CATIII 1000V
NOTE: These meters meet CAT III and CAT IV IEC 61010 standards. The IEC 61010
safety standard defi nes four overvoltage categories (CAT I to IV) based on the magnitude
of danger from transient impulses. CAT III meters are designed to protect against
transients in fi xed-equipment installations at the distribution level; CAT IV meters are
designed to protect against transients from the primary supply level (overhead or
underground utility service).
Maximum voltage between any terminal and earth ground: 1000V DC/AC RMS
Surge Protection: 8kV peak IEC 61010
Display: 4000 counts LCD display, 21mm high
Polarity: Automatic, (-) negative polarity indication.
Over-range: “OL” mark indication.
Low battery indication: A battery “ ”symbol is displayed when the battery voltage drops
below the operating level.
Measurement rate: 2 times per second nominal.
Auto power off: Meter automatically shuts down after approx. 30 minutes of inactivity.
Operating environment: -10 °C to 50 °C (14 °F to 122 °F) at < 70 % relative humidity.
Storage temperature: -30 °C to 60 °C (-4 °F to 140 °F) at < 80 % relative humidity.to
Relative humidity: 90% (0°C to 30°C); 75%(30°C to 40°C); 45%(40°C to 50°C);
For inside use, max height: Operating:3000m, Storage 10,000m
Pollution degree: 2
Safety: The instrument complies with IEC/EN 61010-1:2001 and IEC/EN 61010-031:2002
Power: One 9V battery , NEDA 1604, IEC 6F22.
Dimensions: 182 (H) x 82 (W) x55 (D) mm
Weight: Approx.: 375g.
Accuracy: Accuracy is given at 18 °C to 28 °C (65 °F to 83 °F), less than 70 % RH
DC Voltage
(Auto-ranging)
Input Impedance: 10MΩ.
Maximum Input: 1000V dc or 1000V ac rms.
AC Voltage (Auto-ranging)
Input Impedance: 10MΩ.
AC Response: 50 Hz to 400Hz
Maximum Input: 1000V dc or 1000V ac rms.