![RLS Wacon SYCON 3000 C Operating Manual Download Page 23](http://html1.mh-extra.com/html/rls-wacon/sycon-3000-c/sycon-3000-c_operating-manual_1467170023.webp)
Changing and calling up the programme data
Recorder
19
SYCON
3000 C
8. Recorder
Recorder output RC1 = operational sequence
S t e p n o . : 8 . 1
4 8 1 2 1 6 2 0 m A
A n a l y s i s a c t i v e
▼
►
#
It is possible to connect a recorder or a dot printer to the output RC 1 in order
to log the sequence of operations of the analyser. each function is allotted an
analogue value in the range from 0 to 20 mA. In the case of measuring instru-
ments with a 4 to 20 mA input, values in the range from 4 to 20 mA must be
programmed. The following functions can be registered:
1. Analysis active (mains on)
4. Refill indicator
2. Analysis: soft water
5. Disturbance of the measurement (fault)
3. Analysis: hard water
Note: The different display values are selected with the "
#
" key and changed
with the "#" key.
Recorder output RC2 = water hardness
S t e p n o . : 8 . 2
0 m A = 0 m g / l
2 0
m
A
= 2 0 m
g / l
▼
#
▲
To record the water hardness, it is possible to connect a recorder or a dot
printer to the output RC 2. The water hardness of the last analysis is continu-
ously displayed.
The scale of the display value can be programmed. To this end, a current initial
value of 0 mA or 4 mA must be accorded to the hardness value of 0 degrees.
Furtrhermore, a hardness value must be accorded to the current final value of
20 mA.
Bear in mind the indicator type entered in programme step 1.1 and the associ-
ated measurement range (see also chapter "Recorder output RC 2" on page 9).
1. Define with the help of the "#" key the current initial value 0 mA or 4 mA –
e.g. 0 mA.
2. Press the "
▼
"
key and enter with the help of the "#" and "
►
"
keys the corre-
sponding water hardness for the current final value 20 mA:
e.g. 20 mg/l with indicator type HA 1,2.
ATTENTION!
Check the scale after you have changed the indicator type or the unit of water
hardness in programme steps 1.1 or 1.2.
If the measured value falls below (underruns) the limit, the lower limit of the
measurement range is displayed; if it exceeds (overruns) or in the event of a
fault, the upper limit is displayed.
9.0
Operation sequence
8.1
mA
mA
mA
mA
mA
Analysis:
activ
Analysis:
Soft water
Analysis:
Hard water
Measurement
fault
Indicator
lack
Water hardness
8.2
0 mA
4 mA
20 mA
7.1