AirLink 9850 Gas Monitor Operator’s Manual
Chapter 5: Setup Mode • 33
13. High Alarm Value: Use
ADD
or
SUB
to adjust the high alarm value. The displayed value is in the
appropriate units for each channel. If the selected channel is a %LEL sensor, then the alarm point
values will be in %LEL.
14. Press
MENU
.
15. Duplicate: The AirLink 9850 will ask if you want to duplicate the settings for the remaining
addresses.
•
Press
SUB
(No) to set up the next channel (repeat step 2 - step 15)
•
Press
ADD
(Yes) to duplicate the settings to all consecutive channels. The instrument returns
to the Alarm Settings menu screen. Press
RESET/ESC
to return to Normal Operating Mode.
•
Press
RESET/ESC
to exit Setup Mode
Fault Terminal Setup
1. If necessary, press and hold
MENU
for 6 seconds to enter Setup Mode and then press
ADD
until
the Fault Terminal Setup menu screen appears.
2. Press and release
MENU
to enter the Fault Terminal Setup menu.
3. Failsafe: Press
ADD
or
SUB
to toggle between “Yes” and “No”. When set to “Yes”, the fault
terminals are activated during normal operation and deactivated during a fault. When set to “No”,
the fault terminals are deactivated during normal operation and activated during a fault.
4. Press
MENU
.