SteelConnect SDI-5030 Gateway Hardware Installation Guide
23
3
Replacing SteelConnect Gateway SDI-
5030 Components
This chapter describes how to replace components in the SteelConnect SDI-5030 gateway. It includes
the following sections:
“Field-replaceable units” on page 23
“Required tools” on page 24
“Removing and installing the bezel” on page 24
“Removing and installing the chassis cover” on page 25
“Removing and installing the air duct” on page 26
“Replacing disk drives” on page 27
“Replacing memory modules” on page 30
“Replacing power supply units” on page 32
“Replacing fans” on page 34
“Replacing network interface cards (NICs)” on page 35
Field-replaceable units
The SteelConnect SDI-5030 gateway contains several field-replaceable units (FRUs) that you or a
certified service technician can troubleshoot, remove from the gateway, and replace without having to
send the gateway to a repair facility.
Caution:
Perform troubleshooting or repairs only as directed in the product documentation or by the online or
telephone service and support team. All other servicing should be performed by a certified service technician only.
Your warranty does not cover damage due to servicing that is not authorized by Riverbed. Read and follow the safety
instructions in the
Safety and Compliance Guide
.
Note:
For a list of supported NICs, see
Appendix A, “Supported NICs.”
Important:
If your gateway is rack mounted, see
Chapter 2, “Installing the SteelConnect SDI-5030 Gateway”
to
remove it from the rack before starting the procedures in this chapter.