Please observe the following instructions:
» A total of no more than 0.5 litres of oil may be drawn from a
transformer over its entire service life.
» Oil sampling should only be carried out at temperatures of at
least +5 °C.
» Should problems arise when drawing oil, please contact us
immediately:
Chapter 7 Contact / customer service
» You can obtain the oil sampling set directly from the manufac‐
turer:
Chapter 7 Contact / customer service on page 47
CAUTION
Leakage during operation
In rare cases, leaks may occur during operation of the high voltage
transformer. There is a risk of injury and explosion!
» Regularly inspect the transformer for damage.
» In the event of a malfunction, immediately disconnect the
transformer from the mains and contact the customer service.
3.2 Troubleshooting
In rare cases, faults may occur during operation of the device.
» Disconnect the switchgear from the power supply
2.1.1 Working disconnected from voltage on page 13.
» First check the connections according to the table below.
If the measures listed below do not rectify the fault or if other faults
not listed here occur, please contact us (
ICO 72,5...245
USER MANUAL
When to interrupt the running operation