» Do not touch the primary and secondary terminals under any cir‐
cumstances.
» Always keep the terminal box closed.
» Ensure that the prescribed environmental conditions are main‐
tained during operation,
Chapter 5.2 Environmental conditions
2.6 Shutdown
It is essential to disconnect the transformer and the surrounding
equipment from the power supply.
DANGER
High voltage in conductive components
There is a danger to life through electric shock!
Observe the 5 safety rules of electrical engineering:
» Disconnect the source of high voltage.
» Safeguard against reconnection.
» Ensure no voltage is present.
» Earth.
» Cover or block off adjacent live parts.
For your safety, earth the secondary circuit of the transformer.
Fig. 11: Disconnect the
power source!
ICO 72,5...245
USER MANUAL
How to use this device as intended
23/47