CAUTION
Negligent handling of cleaning agents and preservatives:
There is a risk of harm to health from irritant substances.
» Protective clothing is required when cleaning.
» Wear gloves and protective goggles.
» Observe the safety data sheets for the auxiliary materials.
» Observe the application instructions of the manufacturer of the
auxiliary materials (e.g. SAEKA products: www.saekaphen.de)
If cleaning is required, proceed as follows:
1.
Proceed according to the five rules of electrical engineering!
2.
Clean the insolator with a soap solution (neutral detergent, dis‐
solved in water). Use a cotton cloth for this purpose. Rinse the
surfaces with clear water afterwards.
3.
If using a high pressure cleaner, take care to avoid causing any
damage. Only use equipment with a maximum nozzle pressure of
35 bar for this purpose.
è
In this case the distance between the nozzle and the insulator
must be at least 3 m and the water jet must not be applied to
any one point for longer than 10 seconds at a time.
NOTICE
Re-commissioning after 24 hours at the earliest
After cleaning with any cleaning products, the transformer must
rest for 24 hours and only then be put back into operation.
Fig. 12: Disconnect
mains!
ICO 72,5...245
USER MANUAL
When to interrupt the running operation
25/47