PUB. NO. DFNDRB JANUARY 2013
21
DEFENDER
™
FEATURE RICH - I-COMM INSTRUCTIONS
PROCEDURE FOR USING DOWNLOADER CHIP:
1. Turn power off.
2. Plug in downloader chip.
3. Turn power on.
4. Press ENTER.
5. Scroll to “Copy From Loader”.
6. Press ENTER and UP key to start copy process.
7. When complete, turn power off and remove loader.
8. Restore power and operate door.
PROCEDURE FOR ADJUSTING RECLOSE TIMER:
1. Press ENTER key.
2. Use UP key to scroll to “Set Close Timer”.
3. Press ENTER key.
4. To increase reclose time, press UP key.
5. To decrease reclose time, press DOWN key.
6. Press ENTER when complete.
7. Scroll to EXIT.
8. Press ENTER to save changes.
PROCEDURE FOR CHECKING FAULT HISTORY:
1. Press ENTER key.
2. Use UP / DOWN keys to scroll to “Fault History”.
3. Press ENTER key.
4. This displays the last 5 faults in numerical code.
5. For a detailed view, press the UP key to scroll through the
fault codes.
6. Press ENTER when complete.
7. Scroll to EXIT.
8. Press ENTER, operate door.
The following describes what the fault codes convert to:
Description
Code
#define FaultNone
0
#define FaultPowerUp
1
#define FaultBreakaway
2
#define FaultRunOpenTimer
3
#define FaultMenuInt
4
#define FaultLimitSwitch
5
#define FaultEstop
6
#define FaultRunCloseTimer
7
#define FaultLimitPulseFail
8
#define FaultObstruction
9
#define FaultTimerRead
0A
#define FaultStateOB
0B
#define FaultPROSystem
0C
#define FaultPhotoeye
0D
#define FaultEncoderRead
0E
#define FaultEncoderVelocity
0F
#define FaultEncoderNC
10
CONNECTOR
FLASHING LAMP OUT
UNUSED
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
24VAC INPUT
24VAC COMMON (N)
OPEN/CLOSE COM
CLOSE OUTPUT (K1)
OPEN OUTPUT (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
PIN #
1
2
3
4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
FLASHING LAMP OUT
I-ZONE ALARM OUT
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
24VAC INPUT
24VAC COMMON (N)
OPEN/CLOSE CO
CLOSE OUTPUT (K1)
OPEN OUTPUT (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
UNUSED OUTPUT
I-ZONE ALARM OUT
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
24VAC INPUT
24VAC COMMON (N)
OPEN/CLOSE COM
CLOSE OUTPUT (K1)
OPEN OUTPUT (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
FLASHING LAMP OUT
UNUSED
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
24VAC INPUT
24VAC COMMON (N)
OPEN/CLOSE COM
INVERTER OUT 2(K1)
INVERTER OUT 1 (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
FLASHING LAMP OUT
UNUSED
DC POWER OUT
RESET INPUT (X12)
UNUSED
DC COMMON INPUT
DC POWER INPUT
UNUSED
UNUSED
OPEN/CLOSE COM
CLOSE OUTPUT (K1)
OPEN OUTPUT (K0)
LOOP INPUT 2
LOOP INPUT 1
DC POWER OUT
DC COMMON OUT
DC POWER OUT
LOOP INPUT (X13)
J3
J4
J5
This table shows the function of each of the connectors on the i-COMM controller. The voltages listed for each pin
assume that either the input or output is activated.
Summary of Contents for FROMMELT SAFETY PRODUCTS GUARDIAN DEFENDER
Page 4: ...4 PUB NO DFNDRB JANUARY 2013 DEFENDER GUIDE BASE PLATE POSITIONS ...
Page 18: ...18 PUB NO DFNDRB JANUARY 2013 DEFENDER FEATURE RICH I COMM SETTINGS ...
Page 45: ...PUB NO DFNDRB JANUARY 2013 45 DEFENDER ARCHITECTURAL DRAWING DIRECT DRIVE ...
Page 46: ...46 PUB NO DFNDRB JANUARY 2013 DEFENDER ARCHITECTURAL DRAWING DIRECT DRIVE II ...
Page 47: ...PUB NO DFNDRB JANUARY 2013 47 DEFENDER ARCHITECTURAL DRAWING CHAIN DRIVEN ...