110
Rinnai I
-
Series Condensing Boiler Combi Manual
4.
Place the boiler in operation by either a call for heat or by turning on a Domestic Hot Water
fixture.
5.
The boiler initiates one start
-
up attempt and multiple restart attempts.
After the last start
-
up attempt, the boiler locks out and the gas valve shuts off. Code
110
appears on the controller display which indicates ignition system safety shutoff.
6.
Reconnect the wiring connection to the flame rod. Be careful not to touch the inside of the
wiring connection. To reset the error, press the
DHW
button. The boiler starts up.
1.
Ensure the boiler is not currently firing and the flame rod is not hot.
2.
Remove the boiler front panel.
3.
Disconnect the wiring connection from the flame rod (located on front of the boiler under the burner).
7.
Replace the boiler front panel.
8.
The boiler may now go back into normal operation.
Do not touch the inside of the wiring connection while it is disconnected.
Boiler front side
Burner
Flame Rod
Remove wiring
connection
WARNING