Rinnai cautions against installing the boiler in applications with venting in different
pressure planes. It is possible to have poor performance with this installation.
Slope horizontal exhaust 1/4 in. per foot towards the boiler. DO NOT slope combustion air pipe towards the boiler.
2 in. or 3 in.
PVC/CPVC
IPEX / Royal
Concentric
Side Wall
Termination
Configuration
2 in. or 3 in.
PVC/CPVC
IPEX /Royal
Concentric
Vertical
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC
Snorkel
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC
Standard
Upside Down
"U" Vertical
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC
Elbow or Tee
Side Wall
Termination
Configuration
2 in. or 3 in.
Schedule 40
PVC/CPVC Tee
Vertical
Termination
Configuration
2 in. or 3 in. PVC
Low
Profile
Termination
Configuration
This configuration requires the use of
a Concentric Vent Termination.
Exhaust and
combustion air
MUST NOT be
brought
together into
a single PVC
pipe using a
pipe fitting.
WARNING
Exhaust
Combustion
Air
Single
Pipe
This configuration requires the use of a Concentric
Vent Termination.
CAUTION
Tee not permissible
for intake
termination
Tee not permissible
for intake
termination
Summary of Contents for I Series
Page 124: ...124 Rinnai I Series Condensing Boiler Combi Manual ...
Page 125: ...Rinnai I Series Condensing Boiler Combi Manual 125 ...
Page 134: ...134 Rinnai I Series Condensing Boiler Combi Manual ...
Page 135: ...Rinnai I Series Condensing Boiler Combi Manual 135 ...
Page 136: ...136 Rinnai I Series Condensing Boiler Combi Manual 800000111 3 2019 ...