When the recirculation logic starts, the pump will operate as described below.
•
When the boiler detects the crossover valve is closed, the pump will turn off.
•
After the off interval timer of the boiler has passed, the pump will turn on again.
•
A minimum flow rate 0.5 GPM (2 L/min) is needed for the boiler to operate correctly
(maximum current: 2 Amps). Select the proper pump size based on the crossover valve
and DHW system pressure loss.
Note:
The maximum current permissible to connect to the DHW_Pump connection is 2 Amps.
Timer Connects to T/T 2 Terminal
Cross Over Valve
Cold Water Supply Line
Gas Supply
Building Outlets
Hot Water Supply Line
DHW
Recirculation
Pump
Timer
DHW Recirculation Pump Connect to
“
DHW_Pump Terminal
”
(label on PC Board)