1

 

1.OUTLINE OF THE PRODUCT

 

 

1-1.Preface 

Thank you for purchasing our fixed type Oxygen Detector Head GD-F4A-SC-A. 
First  of  all,  verify  that  the  model  number  of  this  product  is  identical  with  specifications 
described in this manual. This manual is a guide to operation of the GD-F4A-SC-A.    All 
parsons who use this unit for the first time and who has ever used this unit are requested to 
read through the manual to understand the content before use. 

 

1-2.Purpose of use 

This is a suction(flow-through) type oxygen detector head applying the galvanic cell type 
oxygen sensor and is used in combination with indicator / alarm unit to show oxygen content.   
Read the operating manual for indicator / alarm unit as well as this manual.   
This unit is designed as drip-proof construction for outdoor installation.   
Also, it can be used as intrinsically safe system in combination with zener barrier (option) to 
be able to install in hazardous area. 

 
1-3.Definition of DANGER, WARNING, CAUTION and NOTE 

This manual contains the following headings to ensure the safe and effective operation. 

   

This message indicates that improper handling may cause serious 
damage on life, health or assets. 

 

                                                  This message indicates that improper handling may cause serious 

damage on health or assets. 

 

                                                          This  message  indicates  that  improper  handling  may  cause  minor 

damage on health or assets. 

 
 
                                                This message indicates advice on handling. 
                                                         

 

      DANGER 

      WARNING 

      CAUTION 

  *    NOTE 

Summary of Contents for GD-F4A-SC-A

Page 1: ...Oxygen Gas Detector Head GD F4A SC A Operating Manual PT2 152 PT2E 2510...

Page 2: ...tector head 2 Alarm level for gas alarm instrument shall be set within the performance of the instrument Our standard alarm level is 18 by volume for the prevention of oxygen deficiency 3 This is not...

Page 3: ...up 12 How to start the detector head 12 How to exit 12 MAINTENANCE Maintenance intervals and items 13 Calibration Required kit and tools for calibration 14 Performing a zero adjustment 14 Performing...

Page 4: ...or alarm unit to show oxygen content Read the operating manual for indicator alarm unit as well as this manual This unit is designed as drip proof construction for outdoor installation Also it can be...

Page 5: ...nterval Do not change or remodel the circuit structure of this unit Do not disassemble the sensor since there is a electrolyte inside If your finger touches the electrolyte wash your finger away with...

Page 6: ......

Page 7: ...l strip 2 Relayed terminal for input output signal use to the signal converter 4mA adjusting hole VR hole to adjust 4 mA of 4 20mA output factory set SPAN adjusting hole VR hole to adjust SPAN ZERO ad...

Page 8: ...rformance division and group Performance division ia Group C 3 Relations between allowable inductance Lo and allowable capacitance Co of intrinsic safety circuit and external wiring inductance Lw and...

Page 9: ...inside detector head Detector head Indicator alarm unit Non hazardous area Non hazardous area CVVS 1 25mm2 2 core or equivalent MAX 2km 4 20mA Signal converter Sensor lead wire Terminal 4 20mA Cable...

Page 10: ...e to get direct rays of the sun Places closed to high temperature and or emission of electromagnetic wave Place with vibration or shocks Place where the mounting part is weak and it is easy to come ou...

Page 11: ......

Page 12: ...ator alarm unit and be specified that it is for power interruption of indicator alarm unit Ground the zener barrier separately corresponding to the A class grounding with ground resistance of 10 or le...

Page 13: ...se 8 O D 1t copper pipe and so on for piping Carry out piping works as straight as possible Excessively high load may cause burden on the suction pump shortening the effective life of the pump When be...

Page 14: ...en the pump cannot be used If the sample gas pressure would fluctuate use the constant flow rate control valve to keep the constant flow rate Exhaust the sampled gas to open air in principle When make...

Page 15: ...the gas flow be sampled to this unit by turning on the pump switch etc Adjust the flowrate to lead sampled gas to 1 0L 0 3mL min Be sure to perform gas calibration at the time of new installation Corr...

Page 16: ...is also necessary to carry out gas calibration at least every 6 months The law in Japan sets forth that the unit must issue an alarm during the circuit maintenance related to alarm while providing no...

Page 17: ...bration and confirm that the oxygen reading returns to 20 9vol Return disconnected piping to where they were completion of zero adjustment Performing a span adjustment Plug the ammeter to terminal no...

Page 18: ...gen sensor has an enough life span However the actual life is depending on the operating conditions Then replace the sensor once a year as the tentative deadline for the replacement cycle NOTE Output...

Page 19: ......

Page 20: ...temperature 5 10 Environment of low oxygen content Put a sensor into the container and seal off the container List of recommendable spare parts for regular replacement No Name of parts Inspection fre...

Page 21: ...head is relocated select a new place in accordance with 4 2 Precautions for installation points and 4 4 How to install For information on wiring work see 4 5 Caution at wiring construction The unpowe...

Page 22: ...r authorized agent or RIKEN KEIKI Before it is thought to be a trouble Check the wirings around the related instruments as well as this detector head It may be caused by improper operation Re check th...

Page 23: ...barrier MTL7728ac MTL7728 MTL7728 ZB 1A ZB 1A ZB 1A ZB 4A ZB 4A ZB 4A Cabling port Cable gland Applicable cable O D 8 11mm Piping port Rc1 8 with half union for O D 8 1 Operating temperature 10 40 non...

Page 24: ......

Page 25: ...r Safety retainer for explosion protection by limiting the energy of electric current within a non ignition level CVVS This is a kind of connecting cable between indicator alarm unit and oxygen detect...

Page 26: ...Manual Log Rev Amendment Issue data 0 First issue 2018 2 9...