CONFORMITY

Installation and user
guide

Important: Assembly / maintenance of the appliance must be carried out by qualified personnel and in
accordance with applicable laws and regulations.
The manufacturer assumes no responsibility for the use of products that have to comply with particular
environmental and / or installation standards.

Important note
Before connecting the equipment, it is recommended that you read the instruction manual carefully and
keep it for future reference. It is also recommended to perform the electrical connections correctly as
per enclosed drawings, observing the instructions and the Standards.
N.B. Refer to the documentation in all cases where the symbol is on the side

EN 50194
EN 50270

Compliant  EN 60079-29-1

Installation  EN 60079-29-2

Reports issued by  TUV Italia

Channel:  Beinat  gas  solutions

Electric connections also available on

Stand-alone Gas Sensor SG800

                                                          V. R4

The  SG800  is  born  from  the  elegance  and  prestige  that  has  always  distinguished    BEINAT    S.r.l.  and  from
the  home  fitness  concept.
The  probe is a Catalytic gas detection unit with IP66 protection that, together with one of BEINAT’s industrial
type  Control  Units  or  stand-alone,  detects  the  presence  of  esplosive  gas  such  as  Methane,  LPG,  Hydrogen,
Freon,  Chlorine,  Idrogen  Sulphide,    OXYGEN,  and  other  type  of  gas.
The  probe  has  two  danger  levels:
1

st

  LEVEL,  pre-alarm.  This  was  set  at  see  Table  on  page  2

2

nd

  LEVEL,  main  alarm.  This  was  set  at  see  Table  on  page  2

For Oxygen ALARM, for <Oxygen deficiency and > Oxygen Excess

The probe is managed by a microprocessor which not only supplies an alarm signal to the control unit connected
to it, but also allows execution of a self-diagnosis and therefore an AUTOMATIC  CALIBRATION,

 

in order to always

have the maximum detection accuracy.
The self-calibration means the probe adapts in harsh and variable temperature environments, avoiding false alarms
due to anomalous events.
The probe has a 0 ÷ 20 % LEL linear output conforming to the 4 ÷ 20mA standard, for which can be connected
with one of BEINAT's industrial control units.
The important innovation of this probe is:
The possibility to substitute the sensor at the end of the operating cycle or fault by the technician without having
to  send  to  BEINAT  Srl.

Instrument  of  testing  TS1008
To  facilitate  the  reading  of  the  functional  parameters  of  the  probe  as  well  as  the
control  of  annual  operating,  the  BEINAT    S.r.l.    has  built  a  new  portable  tester  TS1008.
The tester allows to read all the data in the memory of the probes eand by serial
transmission, it prints the ticket that confirms the testing data, certifying your own work.

Summary of Contents for SG800

Page 1: ...plosive gas such as Methane LPG Hydrogen Freon Chlorine Idrogen Sulphide OXYGEN and other type of gas The probe has two danger levels 1st LEVEL pre alarm This was set at see Table on page 2 2nd LEVEL main alarm This was set at see Table on page 2 For Oxygen ALARM for Oxygen deficiency and Oxygen Excess The probe is managed by a microprocessor which not only supplies an alarm signal to the control ...

Page 2: ...follow the drawing closely Any use of the detector for purposes other than the intended one is considered improper and as a result of which BEINAT S r l therefore disclaims any responsibility for possible damages caused to people animals or objects TERMS and EXPECTATIONS The installation of the SG800 Probe its ordinary and extraordinary maintenance every six months and its out of service removal a...

Page 3: ...Box unit 2 zones Wall 16 I P 6 5 1 2 Y E S Y E S TAKITJ8 Data Collector Wall 8 I P 6 5 Compatible control units The installation of the detector is not exempt from The compliance with all regulations concerning the characteristics installation and use of gas appliances The ventilation of the spaces and the elimination of combustion products are described in the UNI norms according to ART 3 LAW 108...

Page 4: ... not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Positioning of the Probe Page 4 Detection Diagrams Data NO NO 30 cm Light Gases Light medium gas volatile 30 cm Heav...

Page 5: ...arefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables Electrical connections All relays are voltage free Contact capacity 10A 48VDC resistive SELV C NC NO C NC NO C NC NO 10 9 8 7 6 5 4 3 2 1 Linear output 4 20 mA Powersupply 12 24 V General alarm relay Fault relay Pre alarm relay ...

Page 6: ...1 Vdc If other problems arise the Distributor of BEINAT S r l should be contacted directly Troubleshooting before calling a technician Description and connecting probe SG800 Freon OXYGEN Led ON USB data NC C General Alarm R 5 4 3 2 1 Power supply 12 24 V Linear output 4 20 mA The relay is voltage free Contact capacity 1A 48VDC SELV USB data OXYGEN FREON Linear Otput 4 20 mA 3 2 1 R 0 1 3 2 1 1 VDC...

Page 7: ... all free flames 2 Close the main gas tap or the LPG cylinder tap 3 Do not turn any lights on or off do not turn on any electrical device or appliance 4 Open windows and doors in order to increase ventilation If the alarm stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and ...

Page 8: ...anty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the rec...

Reviews: