Attention!!
The  regulations  described  in  this  paragraph  must  performed  be  authorized  and  specialized  technician  are  suceptibile  to
compromise  the  safety  of  the  survey.
If the device does not start up.
Check  that  the  12/24  Vdc  power  is  present,  and  that  positive  and  negative  polarity  has  not  been  inverted.
If the Fault LED lights up.
If  the  fault  signal  reaches  the  control  unit  connected  to  the  probe.
Check  that  the  cables  are  connected  according  to  the  drawing,  and  that  the  wire  isolation  sheath  has  not  been  pinched.
Check  the  voltage  at  the  terminals  1-2.  It  must  be  higher  than  11Vdc  and  lesser  than  25Vdc.
Check  the  voltage  at  the  terminals  2-3.  It  must  be  from  a  minimum  of  0.8  Vdc  to  a  maximum  of  1.1  Vdc

If  other  problems  arise,  the  Distributor  of  BEINAT    S.r.l.  should  be  contacted  directly.

Troubleshooting

before calling a technician

Description and connecting probe  SG800/Freon - OXYGEN

Led ON

USB data

NC

C

General Alarm

R

5     4     3     2    1

Power supply
  12÷24 V.

Linear output 4-20 mA

The relay is voltage-free.
Contact capacity 1A 48VDC
SELV

USB data

 OXYGEN

FREON

Linear Otput 4-20 mA

3    2    1

R

0

1

3

2

1,1

VDC

Voltmeter

Power Supply
  12÷24 V.

WARNING.

These  measurement  should  be  performed  in
clean air.
Moreover, this test must be performed only with
the probe connected to a control unit, or with a
220 Ohm resistance installed between terminal 2
and terminal 3.

Switch 1 Positive safety
ON 
position: Positive safety  inserted
OFF position: Positive  safety switched off

Switch 2 determination thresholds
ON
 position:
Threshold of intervention from <18.5 to> 23.5 vol

OFF position:
Threshold of intervention from <19.5 to> 22.5 vol

Summary of Contents for SG800

Page 1: ...plosive gas such as Methane LPG Hydrogen Freon Chlorine Idrogen Sulphide OXYGEN and other type of gas The probe has two danger levels 1st LEVEL pre alarm This was set at see Table on page 2 2nd LEVEL main alarm This was set at see Table on page 2 For Oxygen ALARM for Oxygen deficiency and Oxygen Excess The probe is managed by a microprocessor which not only supplies an alarm signal to the control ...

Page 2: ...follow the drawing closely Any use of the detector for purposes other than the intended one is considered improper and as a result of which BEINAT S r l therefore disclaims any responsibility for possible damages caused to people animals or objects TERMS and EXPECTATIONS The installation of the SG800 Probe its ordinary and extraordinary maintenance every six months and its out of service removal a...

Page 3: ...Box unit 2 zones Wall 16 I P 6 5 1 2 Y E S Y E S TAKITJ8 Data Collector Wall 8 I P 6 5 Compatible control units The installation of the detector is not exempt from The compliance with all regulations concerning the characteristics installation and use of gas appliances The ventilation of the spaces and the elimination of combustion products are described in the UNI norms according to ART 3 LAW 108...

Page 4: ... not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Positioning of the Probe Page 4 Detection Diagrams Data NO NO 30 cm Light Gases Light medium gas volatile 30 cm Heav...

Page 5: ...arefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables Electrical connections All relays are voltage free Contact capacity 10A 48VDC resistive SELV C NC NO C NC NO C NC NO 10 9 8 7 6 5 4 3 2 1 Linear output 4 20 mA Powersupply 12 24 V General alarm relay Fault relay Pre alarm relay ...

Page 6: ...1 Vdc If other problems arise the Distributor of BEINAT S r l should be contacted directly Troubleshooting before calling a technician Description and connecting probe SG800 Freon OXYGEN Led ON USB data NC C General Alarm R 5 4 3 2 1 Power supply 12 24 V Linear output 4 20 mA The relay is voltage free Contact capacity 1A 48VDC SELV USB data OXYGEN FREON Linear Otput 4 20 mA 3 2 1 R 0 1 3 2 1 1 VDC...

Page 7: ... all free flames 2 Close the main gas tap or the LPG cylinder tap 3 Do not turn any lights on or off do not turn on any electrical device or appliance 4 Open windows and doors in order to increase ventilation If the alarm stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and ...

Page 8: ...anty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the rec...

Reviews: