Technical   Specifications

Precautions

Power Supply   .................................................................................................... 12÷24VDC           ± 10%
Power demand ................................................................. 90 mA in operating, 160 mA in alarm Max @ 13,8 V
Main Alarm Relay Contact Range  ................................................ 10A 48V resistive - 5A 30Vdc resistive SELV
Pre-Alarm and Fault Relay Contact Range  ................................. 10A 48V resistive - 0,5A 30Vdc resistive SELV
Sensor    ...............................................................................................................................  see  below
Sensitive element  working  range    ......................................................................................  To  100%  of LEL
OXYGEN
Gas  Detection:    ......................................................................................................................  Oxygen
Sensitive  element  working  range,      .....................................................................................  0  -  25  %  di  O

2

Detection  mode Selectable by switch  ............................................... 18%  ÷  20,8%  O

2

 , or   20,8%  ÷ 22,5%  O

2

Analog  output  signal.................................................................................

......  4÷20  mA  standard  tolerance

Selection of the operating Range ................................................................ from 20% of LEL to 100% of LEL
Detector  accuracy  .....................................................................................................................  1%  FS
Long  term shift in clean air   ...................................................................................................  < 3% of LEL
Auto  zero  procedure    ............................................................................  Included  in  the  software algorithms
Response  Time    ............................................................................................................................  <10”
Warm-up  time  ...................................................................................................................  1,30  minutes
Functioning  humidity    .............................................................................................  0-90%  non  condensed
Functioning  temperature    ................................................................................................  -10°C  to  +50°C
Control units usable ............. BX444-Mc, BX449F, GS100M, BX180, BX280,  BX150, GS300-Mc, BX316xp, BX308xp
Max.  distance  between  probe  and  unit    ..........................................................................................  100  m
Cable  diameter  for  connecting  probe    ..............................................................................................  1  mm
Connection: The cable of connection of the probe must not be installed together with the power cables.
Otherwise, make sure to use a shielded cable
Probe’s body material   ............................................................................................................. Alluminium
External  degree  of  protection    ........................................................................................................  IP66
Size    .................................................................................................................................  100x100x60

WARNING!
The  sensor  CATALYTIC  has  a  duration  that  can  vary  from  about  5  to  6  years  in  clean  air.
The  working  temperature  of  the  probe  varies  from    –10°C  to+  50°C.
Each  immediate  puff  of  gas  that  exceeds  100%  of  L.E.L.  takes  away  months  of  life  from  the  sensor.
It  must  do  the  test  of  the  detector  simulating  the  gas  detection  using  a  pre-calibrated  gas  spray.
N.B.  The  operating  test  and  eventual  calibrazine  must  be  performed  at  least  1  time  a  year  by  qualified  technician.

CHECK the integrity of the unit after having removed it from the box.
Check  that  the  data  written  on  the  box  correspond  to  the  type  of  gas  used.
When  doing  the  electrical  connections,  follow  the  drawing  closely.
Any  use  of  the  detector  for  purposes  other  than  the  intended  one  is  considered  improper,
and  as  a  result  of  which  BEINAT  S.r.l.  therefore  disclaims  any  responsibility  for  possible
damages  caused  to  people,  animals  or  objects.
TERMS  and  EXPECTATIONS:  The  installation  of  the  SG800  Probe,  its  ordinary  and
extraordinary  maintenance,  every  six  months,  and  its  out  of  service  removal  at  the  end
of  the  functional  life  guaranteed  by  the  manufacturer,  must  be  carried  out  by  authorized
or specialized personnel.
Do not allow it to become wet.
The  control  unit  can  be  seriously  damaged  as  it  is  not  waterproof  either  when  immersed
in  water  or  exposed  to  high  levels  of  humidity.
Do not drop it.
Heavy  knocks  or  falls  during  transportation  or  installation  can  damage  the  appliance.
Avoid  abrupt  temperature  fluctuations.
Sudden  temperature  variations  can  cause  condensation  and  the  control  unit  could  work  poorly.
Cleaning
Never  clean  the  device  with  chemical  products.  If  necessary,  wash  with  a  moist  cloth.

Code

 

         Type of Gas

                      Sensor

        Working range           Temperature

SG800met

Methane

Catalytic

LEL 0-100%

-10+50°C

SG800gpl

LPG

Catalytic

LEL 0-100%

-10+50°C

SG800idr

Hydrogen

Catalytic

LEL 0-100%

-10+50°C

SG800amX

Ammonia explosive

Catalytic

LEL 0-100%

-10+50°C

SG800amT

Ammonia toxic

Elect. Cell

ppm 0 - 50

-30+50°C

SG800O

2

Oxygen

Optics  fluoresence

depletion/excess

-30+50°C

SG800ace

Acetylen

Catalytic

LEL 0-100%

-10+50°C

SG800vbe

Gasoline

Catalytic

LEL 0-100%

-10+50°C

SG800alc

Alcohol

Catalytic

LEL 0-100%

-10+50°C

SG800ara

White spirit

Catalytic

LEL 0-100%

-10+50°C

SG800eth

Ethanol

Catalytic

LEL 0-100%

-10+50°C

SG800act

Acetone

Catalytic

LEL 0-100%

-10+50°C

SG800hex

Hexane

Catalytic

LEL 0-100%

-10+50°C

SG800eta

Ethyl Acetate

Catalytic

LEL 0-100%

-10+50°C

SG800clo

Chlorine

Catalytic

ppm 0 - 10

-20+50°C

SG800idso2

Hydrogen Sulphide

Elect. Cell

ppm 0 - 15

-20+50°C

SG800fre1

Freon R134A

Semiconductor

ppm 0-5000

-20+60°C

SG800fre2

Freon R404A

Semiconductor

ppm 0-5000

-20+60°C

SG800fre3

Freon R407C

Semiconductor

ppm 0-5000

-20+60°C

SG800fre4

Freon R410A

Semiconductor

ppm 0-5000

-20+60°C

Technical Features  SG800

Summary of Contents for SG800

Page 1: ...plosive gas such as Methane LPG Hydrogen Freon Chlorine Idrogen Sulphide OXYGEN and other type of gas The probe has two danger levels 1st LEVEL pre alarm This was set at see Table on page 2 2nd LEVEL main alarm This was set at see Table on page 2 For Oxygen ALARM for Oxygen deficiency and Oxygen Excess The probe is managed by a microprocessor which not only supplies an alarm signal to the control ...

Page 2: ...follow the drawing closely Any use of the detector for purposes other than the intended one is considered improper and as a result of which BEINAT S r l therefore disclaims any responsibility for possible damages caused to people animals or objects TERMS and EXPECTATIONS The installation of the SG800 Probe its ordinary and extraordinary maintenance every six months and its out of service removal a...

Page 3: ...Box unit 2 zones Wall 16 I P 6 5 1 2 Y E S Y E S TAKITJ8 Data Collector Wall 8 I P 6 5 Compatible control units The installation of the detector is not exempt from The compliance with all regulations concerning the characteristics installation and use of gas appliances The ventilation of the spaces and the elimination of combustion products are described in the UNI norms according to ART 3 LAW 108...

Page 4: ... not be placed near the appliances to be controlled boilers burners industrial kitchens etc but on the opposite wall The probe should not be affected by smoke vapour etc as they could distort their measurement It must be placed away from sources of heat suction fans ventilation fans Positioning of the Probe Page 4 Detection Diagrams Data NO NO 30 cm Light Gases Light medium gas volatile 30 cm Heav...

Page 5: ...arefully follow the instructions and the connections according to Regulations in force keeping in mind that the signal cables should be laid separate from the power cables Electrical connections All relays are voltage free Contact capacity 10A 48VDC resistive SELV C NC NO C NC NO C NC NO 10 9 8 7 6 5 4 3 2 1 Linear output 4 20 mA Powersupply 12 24 V General alarm relay Fault relay Pre alarm relay ...

Page 6: ...1 Vdc If other problems arise the Distributor of BEINAT S r l should be contacted directly Troubleshooting before calling a technician Description and connecting probe SG800 Freon OXYGEN Led ON USB data NC C General Alarm R 5 4 3 2 1 Power supply 12 24 V Linear output 4 20 mA The relay is voltage free Contact capacity 1A 48VDC SELV USB data OXYGEN FREON Linear Otput 4 20 mA 3 2 1 R 0 1 3 2 1 1 VDC...

Page 7: ... all free flames 2 Close the main gas tap or the LPG cylinder tap 3 Do not turn any lights on or off do not turn on any electrical device or appliance 4 Open windows and doors in order to increase ventilation If the alarm stops its cause must be found and the relevant consequent measures taken If the alarm continues and the cause of gas presence cannot be found or removed abandon the building and ...

Page 8: ...anty BEINAT S r l is not liable for possible damage direct or indirect to people animals or things from product faults and from its enforced suspension of use DISPOSAL OF OLD ELECTRICAL ELECTRONIC EQUIPMENT This symbol on the product or its packaging to indicates that this product shall not be treated as household waste Instead it shall be handed over to the applicable collection point for the rec...

Reviews: