Start Aqua Condens 25/60 BIS
34
4.8
Maintenance
Periodic maintenance is essential to the safety, efficiency and lifetime
of the boiler. The appliance must be systematically controlled at reg-
ular intervals to make sure it works correctly and efficiently and con-
forms to legislative provisions in force.
It allows for the reduction of consumption, polluting emissions and
keeping the product reliable over time.
Before starting maintenance operations:
- Perform the analysis of the combustion products to check the boil-
er operation status then cut the electrical supply by turning off the
system's general switch
- Close the fuel and water taps of the heating and domestic hot wa-
ter system.
After performing the necessary maintenance operations, the
original adjustments must be restored and the combustion
product analysis must be performed to check the correct oper-
ation.
4.9
Adjustments
The
Start Aqua Condens 25/60 BIS
boiler is supplied for operation
with Methane gas (G20) and is factory set as shown on the rating
plate.
If adjustments have to be redone, for example after extraordinary
maintenance, after the gas valve replacement or after conversion
from methane gas to LPG and vice versa, the following procedures
must be followed.
The maximum heating electrical value adjustment, the mini-
mum and maximum electrical heating, must be carried out in
the sequence indicated and exclusively by the Riello Technical
Assistance Centre.
- Disconnect the power supply to the boiler
- Turn the heating water temperature selector to its maximum
- Remove the housing and turn the instrument panel (refer to previ-
ous chapters for the detail of the figures)
- Unscrew the fixing screws of the hatch on the terminal board cover
- Insert jumpers JP1 and JP3
-
CN6
CN5
CN12
1
JP1
JP2
JP3
JP4
JP5
JP6
JP7
JP8
CN15
P3
P2
P1
CN13
CN14
SW1
P4
Power up the boiler.
The display shows "ADJ" for about 4 sec.
Proceed with the modification of the following parameters:
1. Absolute/domestic
maximum
2.
Minimum
3.
Maximum heating
4.
Slow ignition
as described below:
- turn the heating water temperature selector to set the desired value
- press the CO button and move on to the next parameter setting.
CN6
CN5
CN12
1
JP1
JP2
JP3
JP4
JP5
JP6
JP7
JP8
CN15
P3
P2
P1
CN13
CN14
SW1
P4
CO button
Live electrical parts (230 Vac).
The following icons are displayed:
1.
during absolute/domestic maximum calibration
during the minimum calibration
during the maximum heating calibration
during the slow ignition calibration
Confirm the adjustment code by pressing the ENTER key
End the procedure by removing the JP1 and JP3 jumpers to store
the set values.