24
INTRODUCTION
4.14.2
Parameters' list
Parameters are listed base on the reference menu.
Reference Menu
M1
Boiler parameters menu
M2
System cascade settings menu
Menu
Par. No.
Nr. dis-
played
Display
Description
Range
Default
setting
UM
Access
type
Category
M1
3
CH set-
point
Defines the desired supply temperature
in heating mode (Par. 1) = 0.
Par. 23 -
Par. 24
158 (70)
°F (°C)
U
Heating
M1
19
Design
Supply
Temp.
Defines the max. set-point at the min-
imum outdoor temperature for climatic
regulation.
86 - 194
(30 - 90)
176 (80)
°F (°C)
U
Heating
M1
20
Design
Outdoor
Temp.
Defines the minimum outdoor tem-
perature to which the maximum
set-point can be associated for climatic
regulation.
-52 - 52
(-25 - 25)
0 (0)
°F (°C)
U
Heating
M1
48
DHW tank
set-point
Establishes the DHW indirect storage
tank set-point Par. 35 in mode 2.
104-160
(40-71)
122 (50)
°F (°C)
U
DHW
M2
72
Permit
Emergency
Mode
Activates the emergency mode. This
mode comes on when communication
between Managing and the primary
circuit's sensor is lost. In this event, if
Par. 72 is set to "Yes", the cascade is
initiated, working to the fixed set-point
determined by Par. 74.
Yes/No
Yes
U
Cascade