![Riello C9514300 Installation, Use And Maintenance Instructions Download Page 8](http://html1.mh-extra.com/html/riello/c9514300/c9514300_installation-use-and-maintenance-instructions_1459447008.webp)
2916050
6
GB
Technical description of the burner
3.1
Technical data
Tab. A
(1)
Reference conditions: Ambient temperature 68 °F (20 °C) - Barometric pressure 394” WC - Altitude 329 ft a.s.l.
(2)
Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
(3)
Equivalent Btu values based on 1 USGPH = 140,000 Btu/hr.
3.2
Electrical data
Fan and pump motor IE3 NEMA Premium Efficiency
Tab. B
3
Technical description of the burner
Model
RL 70/M
RL 100/M
RL 130/M
Output
(1)
High
MBtu/hr
(3)
GPH
1792 - 3136
12.8 - 22.4
2688 - 4480
19.2 - 32
3564 - 5824
25.6 - 41.6
Low
MBtu/hr
(3)
GPH
756 - 1792
5.4 - 12.8
1260 - 2688
9 - 19.2
1568 - 3584
11.2 - 25.6
Fuel
# 2 fuel oil
Operation
Low - high or modulating
Nozzle
number
1 (return flow nozzle)
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °C)
Combustion air temperature
°F max
140 (60 °C)
Pump
delivery (at 290 PSI)
pressure range
fuel temperature
GPH
PSI
° F max
60.8
145 - 304.5
194 (90 °C)
Noise levels
(3)
dB(A)
75
77
78.5
Model
RL 70/M
RL 100/M
RL 130/M
Main electrical supply
Control circuit power supply
V/Ph/Hz
208-230/3/60
120/1/60
Fan and pump motor
rpm
W - HP
V
A
3490
1100 - 1.5
208-230
4
3480
2200 - 3
208-230
7.6
3480
2200 - 3
208-230
7.6
Ignition transformer
V1 - V2
I1 - I2
120 V - 2 X 5 kV
2.7 A - 30 mA
Electrical power consumption
W max
1300
2550
2550
Electrical control circuit consumption
W
750
Total electrical consumption
W
2050
3300
3300
Electrical protection
NEMA 1