40
TYPICAL SYSTEM SCHEMATIC
Menu
Par.
No.
Description
Range
Default setting
INSIEME EVO
COND B/130 LN
UM
Access
2000
2237 Zone 2 mixing valve PID I
0...99
10
I
2000
2238 Zone 2 valve operating time
0...255
2
Sec. x
10
I
2000
2239
Zone 2 setpoint increase
Increases the value of the heating zone setpoint. For
example, if the zone setpoint is 40°C, the heat request
sent to the boiler will be increased by 5°C (factory setting),
therefore the value requested at the boiler will be 45°C.
Valid only for mixed zone.
0...20
5
°C
I
2000
2240 Zone 2 circulator post-circulating time
0...240
30
Sec.
I
2000
2241 Zone 2 delivery overtemperature protection
0...100
55
°C
I
2000
2242 Zone 2 overtemperature control time
0…240
0
Min.
I
2000
2243 Zone 2 overtemperature stand-by time
0…240
2
Min.
I
2000
2244 Zone 2 system reset time
0…240
2
Min.
I
3000
3200
Use of Zone 2 control accessory
0 = NO
1 = Yes
If Zone 2 control accessory is used, AT and OT inputs are not
enabled. AT input is used only to enable the night reduc-
tion on all the active zones (Par. 2001= 2 and 3)
0…1
0
I
3000
3201
Zone 2 mode
0 = direct
1 = mixed
0…1
0
I
Zone 3 Heating Settings
2000
2303
Zone 3 heating setpoint in 0 and 3 heating modes
The thermal unit adjustment determines the boiler set-
point in heating mode, using the highest value among
the requests of all the active zones (Par. 1101, 1201, 1301)
If Zone 3 is set as mixed, the value set in parameter 1312
will be used as the setpoint.
BT: (Par. 2321,
45)
AT: (Par. 2321)
70 (AT)
45 (BT)
°C
U
2000
2319 Zone 3 maximum heating setpoint at the minimum exter-
nal temperature
BT: (Par. 2321,
45)
AT: (Par. 2321)
82 (AT)
45 (BT)
°C
I
2000
2320
Zone 3 minimum external temperature
It defines the minimum external temperature to which
the maximum heating setpoint Par. 2319 must be associ-
ated.
-20…5
-20
°C
I
2000
2321
Zone 3 minimum heating setpoint at basic external tem-
perature (Par. 2322)
It sets the minimum heating setpoint when the external
temperature is equal to the value set in parameter 2322
(basic external temperature).
BT: (20, Par.
2319)
AT: (Par. 2319)
30 (AT)
20 (BT)
°C
I
2000
2322
Zone 3 basic external temperature
It sets the external temperature at which the boiler set-
point must be reduced, according to the value defined in
parameter 2321.
5...30
20
°C
I
2000
2325
Zone 3 summer/winter switching
It blocks the heating request when the external tempera-
ture is greater than this setpoint.
0...35
20
°C
I
2000
2330 Parallel shift of direct Zone/Zone 1 climatic curve
-10…10
0
°C
U
2000
2331 Zone 3 mild climate temperature compensation
0...20
0
°C
I
2000
2332
Zone 3 ambient temperature nominal value
When an OpenTherm (OT) ambient thermostat is connect-
ed to the zone control accessory, this parameter is not
used.
5...35
20
°C
I
2000
2333
Zone 3 setpoint night reduction in heating mode (Par. 2001
= 2 or 3)
It defines by how many degrees the heating setpoint will
be reduced at the opening of the ambient thermostat (AT)
contact
The reduction of the delivery temperature affects all the
active heating zones and it can be used when the AT ter-
minal of every zone regulator is jumpered
0...10
4
°C
I
2000
2334 Compensation factor of Zone 3 external temperature
0...100
50
%
I
2000
2335 Zone 3 mixing valve closing time
0...240
140
Sec.
I
2000
2336 Zone 3 mixing valve PID P
0...99
5
I
2000
2337 Zone 3 mixing valve PID I
0...99
10
I
2000
2338 Zone 3 valve operating time
0...255
2
Sec. x
10
I