TYPICAL SYSTEM SCHEMATIC
3.9
List of parameters
9
The programming lines can be hidden, according to the access level (User, Installer) and to
the thermal unit configuration.
9
The parameters of Installer level must be changed only by the Technical Assistance Service
R
.
Access level:
U:
End user
I: Installer
Key:
DHW
Domestic hot water
HT
High temperature direct circuit
BT
Low temperature mixed circuit
DCW
Domestic cold water
OT
OpenTherm
SA
Ambient probe
SE
Outdoor sensor
TA
Room thermostat
Menu
Par.
No.
Description
Range
Default setting
INSIEME EVO
COND B/130 LN
UM
Access
Main menu
0000
013
Quick adjustment of direct Zone/Zone 1 heating setpoint in
0 and 3 heating modes.
By connecting the zone control accessory, this parameter
can be used to quickly change direct Zone/Zone 1 setpoint.
This parameter simultaneously modifies the value of Par.
2103.
See Par. 2103
See Par. 2103
°C
U
0000
023
Quick adjustment of Zone 2 heating setpoint in 0 and 3
heating modes.
By connecting the zone control accessory, this parameter
can be used to quickly change Zone 2 setpoint. This pa-
rameter simultaneously modifies the value of Par. 2203.
See Par. 2203
See Par. 2203
°C
U
0000
033
Quick adjustment of Zone 3 heating setpoint in 0 and 3
heating modes.
By connecting the zone control accessory, this parameter
can be used to quickly change Zone 3 setpoint. This pa-
rameter simultaneously modifies the value of Par. 2303.
See Par. 2303
See Par. 2303
°C
U
0000
047
Quick adjustment of DHW setpoint with heater
This parameter is only visible with Par. 2035 = 1
See Par. 2047
°C
U
0000
200
Test mode
0 = None
1 = Stops the chimney sweep function
2 = Starts the chimney sweep function
0…2
0
I
0000
201
Stops the venting function
0 = No action
1 = Stop venting
Visible only when de-aeration is in operation
0…1
0
U
0000
901
Unit of measurement for temperature
0 = °C
1 = °F
0...1
0
I
0000
902
Pressure unit of measurement
0 = BAR
1 = PSI
0...1
0
I
Info menu
1000
1001 CH flow temperature
°C
U
1000
1002 Domestic hot water temperature
°C
U
1000
1004 Outdoor temperature
°C
U
1000
1006 Displays the flue temperature
°C
U
1000
1007 Return temperature
°C
U
1000
1033 System pressure
bar
U
1000
1056 Total hours of operation in heating mode
h x
10
U
1000
1057 Total hours of operation in domestic mode
h x
10
U
1000
1058 Total hours of operation
h x
10
U
1000
1062 Displays the flow meter flow rate
Display active only with Par. 2027 = 1
l/min.
U
1000
1063 Input signal 0-10V
V
U
1000
1090
Counts down the days to the next service (if it’s past, a
negative value is shown)
If the value is < 15 the service icon flashes
Days
U
1000
1101
Direct Zone/Zone 1 delivery temperature
°C
U
1000
1102 Direct Zone/Zone 1 ambient temperature
°C
U