TYPICAL SYSTEM SCHEMATIC
Menu
Par.
No.
Description
Range
Default setting
INSIEME EVO
COND B/130 LN
UM
Access
1000
1112
Zone 1 heating setpoint
°C
U
1000
1201 Zone 2 delivery temperature
°C
U
1000
1202 Zone 2 ambient temperature
°C
U
1000
1212
Zone 2 heating setpoint
°C
U
1000
1301 Zone 3 delivery temperature
°C
U
1000
1302 Zone 3 ambient temperature
°C
U
1000
1312
Zone 3 heating setpoint
°C
U
Heating general settings
2000
2001
Heating operating mode
0 = Operation with fixed setpoint and ambient thermostat
1 = Operation with climatic curve and ambient thermostat
2 = Continuous operation with climatic curve and night
reduction with ambient thermostat
3 = Continuous operation with fixed setpoint and night
reduction with ambient thermostat
4 = Operation with variable setpoint with input signal
0-10V
0…4
0
I
2000
2005 Circulator post-circulating time in heating mode
10…900
120
Sec.
I
2000
2007 Switch-off hysteresis in heating mode
0…5
3
°C
I
2000
2008 Ignition hysteresis in heating mode
0…5
3
°C
I
2000
2009
Burner restart time
It defines the stand-by time for a subsequent restart
after a switch-off, regardless of the delivery temperature
decrease. If it goes below the value set in Par. 2010 the
thermal unit remains on.
10...900
180
Sec.
I
2000
2010
Temperature differential for burner restart
It defines the temperature difference below which the
burner restarts regardless of the elapsed time indicated in
Par. 2009.
0...20
16
°C
I
2000
2011
Temperature differential for the deactivation of the burn-
er’s second stage in heating mode
This parameter can only be seen on boilers with a dual
stage burner
0…10
5
°C
I
2000
2012
Burner second stage ignition hysteresis in heating mode
This parameter can only be seen on boilers with a dual
stage burner
0…10
5
°C
I
2000
2013
Temperature differential for the deactivation of the burn-
er’s second stage in DHW mode
This parameter can only be seen on boilers with a dual
stage burner
0…10
5
°C
I
2000
2014
Burner second stage ignition hysteresis in DHW mode
This parameter can only be seen on boilers with a dual
stage burner
0…10
5
°C
I
2000
2016 Heating pump proportional part PID
0...100
20
I
2000
2017 Heating pump additional part PID
0...600
50
I
2000
2018 Heating pump derivative part PID
0...100
50
I
2000
2019 Heating flow meter minimum flow rate
Setting a value = 0 deactivates the function
0…200
5
l/min.
I
2000
2020
Type of flow meter
1= HUBA DN15
2= HUBA DN20
3= HUBA DN25
4= HUBA DN32
1...4
1
I
2000
2021 Number of days to next service
365
Days
U
2000
2022
Service reminder
This function reminds the user of the need to carry out a
programmed service on the boiler, after the number of
days set in Par. 2021
0 = Deactivates the function
1 = Activates the function
2 = Resets the countdown of days to next service to zero
0…2
0
U
2000
2023 Minimum heating setpoint
20,Par. 2024
20
°C
I
2000
2024 Maximum heating setpoint
Par. 2023,90
82
°C
I
2000
2025 Minimum 0-10V input voltage in heating mode Par. 2001=
4
0...10
1
V
I
2000
2026 Maximum 0-10V input voltage in heating mode Par. 2001=
4
0...10
9
V
I