Operation, indication, diagnostics
65
20093868
GB
8.3.2
First startup with a new program module or in
case of replacement of program module
Display shows alternately
rSt
and
PrC
.
Display shows the replacement of the program module.
Signal lamp blinks red once and yellow twice alternately.
Press
for >3 seconds to start data download from the program module.
Signal lamp blinks yellow.
The process of 3 seconds is supported by a short flash of the yellow signal lamp.
Note:
If you press
for <3 seconds, data download does not start. To start the restore process again, the
LME7... must be reset by switching mains ON/OFF.
Display shows run during download (restore process) of the program sequence.
Display shows alternately End and rSt.
Display shows the end of data exchange.
After 2 minutes, the unit changes to
Loc 138
After the restore process, the unit is automatically in the lockout position (LOC 138) and must be reset for
operation!
Press
for >1 second to reset the unit.
Display:
OFF
Alternately
nfo
>3 s
nfo
nfo
Alternately
Alternately
nfo
>1 s
nfo
WARNING
On first startup or after exchange of the pro-
gram module, the sequence of functions and
parameter settings must be checked upon com-
pletion of the restore process.