Technical description of the burner
7
20093868
GB
3.1
Technical data
Tab. A
(1)
Reference conditions: ambient temperature 68 °F (20°C) - Barometric pressure 394” WC - Altitude 329 ft.
(2)
Pressure at test point 6)(Fig. 9 at page 11) with zero pressure in the combustion chamber and maximum burner output.
3.2
Electrical data
Tab. B
3.3
Burner models designation
Tab. C
3
Technical description of the burner
Model
RX 700 S/PV
RX 850 S/PV
RX 1000 S/PV
Output
(1)
Delivery
(1)
max.
MBtu/hr
kW
2700
781
3250
940
4535
1330
min.
MBtu/hr
kW
450
132
565
165
800
235
Fuel
- Max. delivery
- Gas head pressure at max. delivery
(2)
- Supply pressure
type
SCFH
“wc
“wc
Natural gas
Propane
2700
1080
- 0.45
- 0.29
7 - 14
7 - 14
Natural gas
Propane
3250
1300
- 0.91
- 0.63
7 - 14
7 - 14
Natural gas
Propane
4535
1814
- 1.9
- 0.96
7 - 14
7 - 14
Operation
Modulating
Standard applications
Boilers: water, steam, thermal oil
Ambient temperature
°F
32 - 104 (0 - 40 °C)
Combustion air temperature
°F max
140 (60 °C)
Model
RX 700-850 S/PV
RX 700-850 S/PV
RX 1000 S/PV
Control circuit power supply
V/Ph/Hz
120/1/60
Main power supply (+/- 10%)
V/Ph/Hz
120/1/60
208-240/1/60
460/3/60
Fan motor
rpm
V
W
HP
A
4800
115 (100...130)
1200
1.61
13
4800
230 (208...240)
1150
1.54
5.7
6100
400(380...480)
2400
3.22
4.0
Ignition transformer
V1 - V2
I1 - I2
120 V - 2x12 kV
0.51 A - 30 mA
Electrical power consumption
W
1200
1150
2400
Electrical control circuit consumption
W max
750
750
750
Total electrical consumption
W
1950
1900
3150
Electrical protection
NEMA 1
Model
Code
Voltage
Fan motor starting
Flame safeguard
RX 700 S/PV
20092672
120/1/60
Direct
Burner mounted
20092651
208-240/1/60
RX 850 S/PV
20092611
120/1/60
Direct
Burner mounted
20092613
208-240/1/60
RX 1000 S/PV
20082125
460/3/60
Direct
Burner mounted