page 77 / 84
0MLMHTM30RUENUA
9
General characteristics
UPS models
300kVA
400kVA
500kVA
MECHANICAL DATA
Width (inches [mm])
59 [1500]
Width (inches [mm]) TCE version *
74,80 [1900]
Height (inches [mm])
74,80 [1900]
Depth / height (inches [mm])
39.70 [1000]
Ventilation
Air Forced
Noise at 1m from front (0÷100%
load)(dBA)
72
Applicable Standards
UL Standard 1778 5
th
edition
CUL to CSA C22.2
UL 60950-1
National Electrical Code (NFPA-70)
FCC Part 15 Subpart J Class A
EN 62040-1; EN 62040-2 (C3); IEC / EN 62040-3
Version including Top Cable Entry cabinet
UPS models
300kVA
400kVA
500kVA
INPUT RECTIFIER
Rated voltage
480Vac 3-phase
Rated voltage tolerance (%), with
battery recharge, depending on the load
percentage
-10%, +10% (100% load)
-20%, +10% (85% load)
-30%, +10% (75% load)
-40%, +10% (65% load)
Input frequency tolerance
from 45 to 65Hz
Rated current (480 V) [A]
361A
481A
601A
Rated power (480 V)-(kVA)
320
425
484
Maximum current at full load and with
battery recharging
[A]
433A
640A
640A
Power factor at rated voltage (480 V)
and battery charge from 25% to 100%
of the load
>0.99
Current Harmonic Distortion (THDi)
(with mains distortion <1%)
Load from 75% to 100 %
load at 50 %
load at 25 %
≤ 3
< 5
< 8
Progressive start of rectifier (Power
Walk-in)
from 0 to 125 seconds (configurable)
Delay of progressive start of rectifier
(Power Walk-in delay timer))
from 0 to 125 seconds (configurable)