page 71 / 84
0MLMHTM30RUENUA
-
Three UPS in parallel
D UPS1 LED on, UPS2 LED off, UPS3 LED off
E SW1 in start position on UPS1, SW1 in cont position on UPS2 and UPS3
Note: 3 RJ45 cables are required despite redundancy. System will not start up unless 3 cables are installed.
To add other parallel UPS’s, a “
UPS PARALLEL CABLE” must be added for each new UPS connected
.
The signal connection must not be removed when one UPS is shut down
B
B
C
A
UPS 1
D
A
UPS 2
E
A
UPS 2