page 13 / 84
0MLMHTM30RUENUA
2.
Slide away the carton from above.
3.
Remove the screws securing the cabinet to the wooden base.
4
Installation environment
The UPS and the battery cabinet have been designed for indoor installation. The choice of premises for
installation should comply with the points set out below.
4.1
Ambient conditions:
ensure that the floor can support the weight of the MASTER HP - UL and of any battery cabinet that
may be used
avoid dusty environments (the indoor area must be free of conductive contaminations)
avoid narrow environments that could hinder normal maintenance operations
avoid placing the unit in areas exposed to direct sunlight or heat
ensure that the ambient temperature conforms to the following:
-
minimum operating temperature:
+32°F ( 0 °C)
-
maximum temperature for 8 hours a day:
+104°F (+ 40°C)
-
average temperature for 24 hours:
+95°F (+ 35°C)
4.2
Dimensions of the premises
For the Maintenance dimensions of the cabinets, refer to the
“INSTALLATION DRAWINGS”
supplied with the
UPS and with the battery cabinet, if present. These drawings provide the following data:
Position of the holes in the base to secure the unit to the floor, if applicable;
View of the floor support for the sizing of a structure to raise the cabinet, if applicable;
Position of cable entry;
Position of the fans on the top of the UPS, for the positioning of a structure to convey the warm air
discharged by the equipment outside the premises, if applicable;
Input, output and battery cables section;
Losses of the power dissipated by the equipment (kW).