6.1.5.15 IDENT.
Press the following sequence of keys to access the menu: 3, 5, 436215, 7, 7:
Press key 1 to exit the menu. Keys 7 and 8 can be used to decrease or increase the number used for the identification of
a single unit in systems with several UPS connected to a single RS232 serial line. The basic number is 0 and may be
changed between values from 0 to 7.
6.1.5.16 OPERATION IN STANDBY-ON
Press the following sequence of keys to access the menu: 3,5,436215,8:
Stby= 2sec. Stby_ON= 0
Adjustment: 4=Sma.ON, 5-,6+ 7=-,8=+
Press key 1 to exit the menu. Press key 8 Stby=1 to change the UPS from ON-LINE mode to STANDBY-ON mode.
Press key7 to change the UPS from STANDBY-ON mode to ON-LINE mode. The switch onto the bypass line may be
immediate when “Stby = 0 min.” or delayed by means of keys 5 and 6. The backup line must be available for the time
set within the acceptance field before the switchover can take place (see “PERSONALIZ. BYPASS VOLTAGE
FIELD” menu). The setting remains stored even during a shutdown due to a power failure. For a description of the
operation see the section “SETTING MODES”.
6.1.5.17 SMART ACTIVE OPERATION
Press the following sequence of keys to access the menu: 3,5,436215,8,4:
SMART ACTIVE S. Stby = 5 min. Stby_ON = 1
Adjustment: 4=Sma.OFF, 5-,6+ 7 = -, 8 = +
Press key 1 to exit the menu. When the Smart Active function is activated via key 4, Stby_ON goes to 1. The setting
remains stored even during a shutdown due to a power failure. There is a delay of 5 minutes before transfer to SMART
ACTIVE mode. For a description of the operation see the section “SETTING MODES”.
When the code is inserted the basic menu becomes:
NORMAL OPERATION SMART A.
P200, M OUT= 99%VA, BATT= 100%Ah, 5=ON
6.1.5.18 INVERTER-OFF/BYPASS
Press the following sequence of keys to access the menu: 3, 6 :
Exit the menu by pressing key 8 or any other key with a sequence other than the one described here. Pressing keys 4, 7,
2, 6, 3 in succession as shown on the display activates the command for bypass with shutdown of the inverter. The
command is executed after a few seconds’ delay to allow for cancellation. When this command is active, the following
alarm is shown on the display:
"BYPASS COMMAND ACTIVE; 8=DEACTIV. ".
To return to normal operation, including after system shutdown, the command has to be cancelled by pressing key 8, or
by sending the key code through the RS232.
NOTE To mask the command code 47263, insert code 436213 on the panel from the PERSONALIZATIONS menu
(keys 3, 5). Repeat the operation to display the code again.