page 61 / 84
0MLMHTM30RUENUA
The "RECORDED CODES" menu is accessed with key 6 from menu 4 "RECORDED EVENTS" and menus 4, 2; 4, 2,
2; 4,2,2,2 that is, the recorded measurement menus. Return to the basic menu by means of key 1.
Apart from key 6, the other keys have the same functions as those described for menu 4, and the messages on the lower
line also remain the same.
The upper line: s=FFFF c=FFFF b=FFFF r=FFFF-FF i=FFFF-FF, shows the internal codes recorded at the time of the
event.
Use key 6 to return to menu 4 while keeping the current event; you can then switch several times from the description
of the event with the "stored alarm message" to the one with the internal codes.
1.1.1.3
RECORDED value on full page
The "RECORDED value on full page " menu is accessed with key 4 from menu 4.
On this page, when the “stop” key is not cross marked, are shown all present measurements and internal codes, and the
past measurements when the “stop” key is marked.
When the “STOP” key is cross marked it is possible to look to the other past value recorded by arrow keys.
This key switch to the page showing the message and codes of 4 past events and it is possible to look to the other
past events by arrow keys.
This key switch to page with all codes and measurements displayed of 1 event.
The key “6” switch from code with message line to full lines code.
NORMAL OPERATION
a=0000-0000 2011- 1-24/15:35: 40;
----------------------------------------------------------
s=8000 c=0000 b=0000 r=0000-00 i=0000-00
====================================
IN=100,100,100%V; 45, 45, 45%A; 60.2Hz
BY=277,277,277Vln (480V);60.0Hz;
----------------------------------------------------------
OUT= 277,277,277Vln(480V); 50, 50, 50%A
40, 40, 40%W 60.0Hz; 57, 57, 57%Ap
----------------------------------------------------------
Bat=530V; - 11A; i=277,277,277Vln;720Vdc
Ts=26,Tr=36,Ti=35;
NORMAL OPERATION
a=0000-0000 2011- 1-24/15:35: 40;
----------------------------------------------------------
s=8000 c=0000 b=0000 r=0000-00 i=0000-00
====================================
IN=100,100,100%V; 45, 45, 45%A; 60.2Hz
BY=277,277,277Vln (480V);60.0Hz;
----------------------------------------------------------
OUT= 277,277,277Vln(480V); 50, 50, 50%A
40, 40, 40%W 60.0Hz; 57, 57, 57%Ap
----------------------------------------------------------
Bat=530V; - 11A; i=277,277,277Vln;720Vdc
Ts=26,Tr=36,Ti=35;
NORMAL OPERATION
a=0000-0000 2011- 1-24/13:35: 0;n120
------------------------------------------------------
BYPASS LINE VOLTAGE FAIL or SWBY OFF
a=0400-0000 2011- 1-24/13: 5: 5;n119
------------------------------------------------------
PREALARM, LOW BATTERY VOLTAGE
a=1C00-0000 2011- 1-24/13: 1: 3;n118
------------------------------------------------------
MAIN LINE VOLTAGE FAIL or SWIN OFF
a=1800-0000 2011- 1-24/12: 1: 1;n117
------------------------------------------------------
NORMAL OPERATION
a=0000-0000 2011- 1-24/11: 4:18;n116
6
s=8000 c=0000 b=0000 r=0000-08 i=0000-00
a=0000-0000 2011- 1-24/13:35: 0;n120
------------------------------------------------------------
s=8000 c=0000 b=3C20 r=0000-08 i=0000-00
a=0400-0000 2011- 1-24/13: 5: 5;n119
------------------------------------------------------------
s=8000 c=0000 b=0000 r=F881-00 i=0000-00
a=1C00-0000 2011- 1-24/13: 1: 3;n118
------------------------------------------------------------
s=8000 c=0000 b=0000 r=F881-00 i=0000-00
a=1800-0000 2011- 1-24/12: 1: 1;n117
------------------------------------------------------------
s=8000 c=0000 b=0000 r=0000-08 i=0000-00
a=0000-0000 2011- 1-24/11: 4:18;n116
6