6
TECHNICAL DATA
(1) Reference conditions: Ambient temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m s.l.m.
(2) Pressure at test point 17)(A)p.8, with zero pressure in the combustion chambre, with open gas ring 2)(B)p.12 an maximum burner output
(3) Sound pressure measured in manufacturer’s combustion laboratory, with burner operating on test boiler and at maximum rated output.
ACCESSORIES
(optional):
•
KIT FOR LPG OPERATION
•
OUTPUT POWER REGULATOR KIT:
Under modulating operation, the burner automatically adapts to one of an infinite number of firing rates
between the low and high flame output positions, thus ensuring stable operating conditions in terms of temperature or pressure. Two components
should be ordered: • Power regulator to install to the burner • Probe to install to the boiler.
•
GAS TRAIN ACCORDING TO REGULATION EN 676 (with valve, pressure governor and filter):
see page 18.
MODEL
RS 190/M
TYP
836 T1
OUTPUT
(1)
MAX.
kW
1279 - 2290
1100 - 1970
Mcal/h
MIN.
kW
470
405
Mcal/h
FUEL
NATURAL GAS: G20 - G21 - G22 - G23 - G25
G20
G25
- net calorific value
kWh/Sm
3
Mcal/Sm
3
9.45
8.2
8.13
7.0
- absolute density
kg/Sm
3
0.71
0.78
- max. delivery
Sm
3
/h
230
267
- pressure at max. delivery
(2)
mbar
15
22
OPERATION
• On-Off (1 stop min each 24 hours).
This burner is also fitted for the continuos operation, if it is equipped with
the control box LANDIS type LGK 16.333 A27 (interchangeable with the
burner control box Landis LFL 1.333).
• Progressive two-stage or modulating by kit (see ACCESSOIRES).
STANDARD APPLICATIONS
Boilers: water, steam, diathermic oil
AMBIENT TEMPERATUR
°C
0 - 40
COMBUSTION AIR TEMPERATURE
°C max
60
ELECTRICAL SUPPLY
V
Hz
230 - 400 with neutral ~ +/-10%
50 - three-phaes
ELECTRIC MOTOR
rpm
W
V
2800
4500
220/240 - 380/415
Running current
A
15.8 - 9.1
Start-up current
A
126 - 72.8
CONTROL BOX
LFL 1.333
IGNITION TRANSFORMER
V1 - V2
I1 - I2
230 V - 1 x 8 kV
1 A - 20 mA
ELECTRICAL POWER CONSUMPTION
W max
5500
ELECTRICAL PROTECTION
IP 44
IN CONFORMITY WITH EEC DIRECTIVES
90/396 - 89/336 - 73/23
NOISE LEVELS
(3)
dBA
83.1
APPROVAL
CE
0085AT0042
COUNTRY
CATEGORY
IT - AT - GR - DK - FI - SE
II
2H3B/P
ES - GB - IE - PT
II
2H3P
NL
II
2L3B/P
FR
II
2Er3P
DE
II
2ELL3B/P
BE
I
2E(R)B
, I
3P
LU
II
2E3B/P
BURNER
RS 190/M
OUTPUT
kW
465 ÷ 2290
CODE
3010166
PARAMETER TO BE CHECKED
PROBE
POWER REGULATOR
Range
Type
Code
Type
Code
Temperature
- 100...+500°C
PT 100
3010110
RWF40
3010212
Pressure
0...2,5 bar
0...16 bar
Output probe
4...20 mA
3010213
3010214
GB