background image

40

(1) The control box 13)(A)page 8 is fitted with a disc  which rotates during the firing programme, which can be seen through the transparent lock-out reset button.

When the burner does not fire or comes to halt following a fault, the symbol which appears behind the reset button indicates the type of problem.

(2) The fuse is located in the rear part of the control box 13)(A)page 8. A pull-out fuse is also available as a spare part which can be fitted after breaking the tag on the

panel which holds it in place.

SYMBOL (1)

FAULT

PROBABLE CAUSE

SUGGESTED REMEDY

The burner does not start

1

- No electrical power supply  . . . . . . . . . . . . . . . . . . . . . . . . . Close all switches - Check connections

2

- A limiter control device is open . . . . . . . . . . . . . . . . . . . . . . Adjust or replace

3

- A safety control device is open . . . . . . . . . . . . . . . . . . . . . . Adjust or replace

4

- Control box lock-out  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset control box

5

- Control box fuses blown  . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace (2)

6

- Erroneous electrical connections  . . . . . . . . . . . . . . . . . . . . Check connections

7

- Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace

8

- No gas supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Open the manual valves between meter and 

train

9

- Mains gas pressure insufficient . . . . . . . . . . . . . . . . . . . . . . Contact your GAS COMPANY

10 - Minimum gas pressure switch fails to close  . . . . . . . . . . . . Adjust or replace
11 - Air pressure switch in operating position  . . . . . . . . . . . . . . Adjust or replace
12 - Cam II servomotor contact does not operate  . . . . . . . . . . . Adjust cam II or replace servomotor

control box terminals 11-8

The burner does not start and a 
function lock out occurs

13 - Flame simulation   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace control box
14 - Defective motor remote control switch  . . . . . . . . . . . . . . . . Replace
15 - Defective electrical motor  . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
16 - Motor protection tripped  . . . . . . . . . . . . . . . . . . . . . . . . . . . Reset thermal cut-out when third phase is re-

connected

The burner starts but stops at 
maximum gate valve setting

17 - Cam I servomotor contact does not operate . . . . . . . . . . . . Adjust cam I or replace servomotor

control box terminals 9-8

The burner starts and then locks 
out

Air pressure switch inoperative due to
insufficient air pressure:

18 - Air pressure switch adjusted badly . . . . . . . . . . . . . . . . . . . Adjust or replace
19 - Pressure switch pressure point pipe blocked  . . . . . . . . . . . Clean
20 - Head wrongly adjusted . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust

The burner starts and then locks 
out

21 - Fault in flame detection circuit. . . . . . . . . . . . . . . . . . . . . . . Replace control box

The burner stays in the pre-purge 
stage

22 - Cam III servomotor contact does not operate . . . . . . . . . . . Adjust cam III or replace servomotor

control box terminals 10-8

After pre-purge and safety time, 
the burner goes to lock-out and 
the flame does not appear

23 - The solenoid VR allows little gas through . . . . . . . . . . . . . . Increase
24 - Solenoid valves VR or VS fail to open  . . . . . . . . . . . . . . . . Renew the coil or rectifier panel
25 - Gas pressure too low  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Increase pressure at governor
26 - Ignition electrode wrongly adjusted . . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p.14
27 - Electrode grounded due to broken insulation . . . . . . . . . . . Replace
28 - High voltage cable defective . . . . . . . . . . . . . . . . . . . . . . . . Replace
29 - High voltage cable deformed by high temperature . . . . . . . Replace and protect
30 - Ignition transformer defective  . . . . . . . . . . . . . . . . . . . . . . . Replace
31 - Erroneous valve or transformer electrical connections . . . . Check
32 - Control box defective  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace
33 - A cock down-line of the gas train is closed . . . . . . . . . . . . . Open
34 - Air in pipework. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bleed air

The burner goes to lock-out right 
after flame appearance

35 - The solenoid VR allows little gas through . . . . . . . . . . . . . . Increase
36 - Ionisation probe wrongly adjusted. . . . . . . . . . . . . . . . . . . . Adjust, see fig. (C)p. 14
37 - Faulty electrical connections for probe . . . . . . . . . . . . . . . . Repeat connection
38 - Insufficient ionisation (less than 6 mA) . . . . . . . . . . . . . . . . Check probe position
39 - Probe grounded  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Withdraw or replace cable
40 - Max. gas pressure switch operates. . . . . . . . . . . . . . . . . . . Adjust or replace
41 - Defective control box. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace

The burner repeats the starting 
cycle without lock out

42 - Mains gas pressure is near the value to which the . . . . . . . Reduce operating pressure

min. gas pressure switch gas is adjusted. The

of minimum gas pressure

repeated drop in pressure which follows valve

switch.

opening causes temporary opening of the pressure

Replace gas filter

switch itself, the valve immediately closes and the
burner comes to a halt. Pressure increases again, the
pressure switch closes again and the firing cycle is
repeated. The sequence repeats endlessly.

Ignition with pulsation

43 - Flame simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Replace control box

During operation, the burner stops 
in lock out

44 - Probe or ionisation cable grounded  . . . . . . . . . . . . . . . . . . Replace worn parts
45 - Fault on air pressure switch  . . . . . . . . . . . . . . . . . . . . . . . . Replace
46 - Max. gas pressure switch operates. . . . . . . . . . . . . . . . . . . Adjust or replace

Lock out when burner stops

47 - Flame remains in combustion head  . . . . . . . . . . . . . . . . . . Eliminate persistence of flame

or flame simulation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . or replace control box

The burner does not pass to 2nd 
stage

48 - Poorly adjusted head  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Adjust, see page 17
49 - Ignition electrode wrongly adjusted . . . . . . . . . . . . . . . . . . . Adjust, see fig. (C),page 14
50 - Poorly adjusted fan air gate: too much air. . . . . . . . . . . . . . Adjust
51 - Output during ignition phase is too high  . . . . . . . . . . . . . . . Reduce

P

1

Summary of Contents for 836 T1

Page 1: ...tori di gas ad aria soffiata Gebl se Gasbrenner Blown type gas burners Br leurs gaz air souffl 2916148 2 03 2007 CODICE CODE MODELLO MODELL MODEL MODELE TIPO TYP TYPE TYPE 3866206 RS 190 M 836 T1 I D...

Page 2: ...olgenderma en bezeichnet 1 A Detail 1 der Zeichnung A auf der gleichen Textseite 1 A p 4 Detail 1 der Zeichnung A auf Seite 4 D CONTENTS TECHNICAL DATA page 6 Accessories 6 Burner description 9 Packag...

Page 3: ...nsit assoluta kg Sm3 0 71 0 78 portata massima Sm3 h 230 267 pressione alla portata massima 2 mbar 15 22 FUNZIONAMENTO Intermittente min 1 arresto in 24 ore Questo bruciatore adatto anche al funzionam...

Page 4: ...78 H chstdurchsatz Sm3 h 230 267 Druck bei H chstdurchsatz 2 mbar 15 22 BETRIEB Aussetzend min 1 Halt in 24 Std Wenn dieser Brenner mit dem Gasfeuerungsautomaten Landis Gyr LGK 16 333 A27 ausgestattet...

Page 5: ...0 absolute density kg Sm3 0 71 0 78 max delivery Sm3 h 230 267 pressure at max delivery 2 mbar 15 22 OPERATION On Off 1 stop min each 24 hours This burner is also fitted for the continuos operation i...

Page 6: ...45 8 2 8 13 7 0 densit absolue kg Sm3 0 71 0 78 pression au d bit max Sm3 h 230 267 pression au d bit max 2 mbar 15 22 FONCTIONNEMENT Intermittent 1 arr t min en 24 heures Ce br leur est appropri auss...

Page 7: ...l fissaggio ventilatore al manicotto 23 Condotto arrivo gas 24 Valvola farfalla gas 25 Flangia per il fissaggio alla caldaia 26 Disco di stabilit fiamma 27 Staffa per l applicazione del regolatore di...

Page 8: ...crews securing fan to sleeve 23 Gas input pipework 24 Gas butterfly valve 25 Boiler mounting flange 26 Flame stability disk 27 Bracket for mounting the power regulator RWF40 28 Socket for electrical c...

Page 9: ...e di prova secondo la norma EN 676 Riportiamo in B diametro e lunghezza della camera di combustione di prova Esempio Potenza 650 Mcal h diametro 60 cm lunghezza 2 m CALDAIE COMMERCIALI C L abbinamento...

Page 10: ...rates were set in relation to special test boilers according to EN 676 regulations Figure B indicates the diameter and length of the test combustion chamber Example Output 650 Mcal h diameter 60 cm le...

Page 11: ...alla potenza MAX Gas naturale G 20 PCI 9 45 kWh Sm3 Pressione del gas alla presa 1 B 11 0 mbar Pressione in camera di combustione 3 0 mbar 11 0 3 0 8 0 mbar Alla pressione 8 0 mbar colonna 1 corrispo...

Page 12: ...re value to your result in column 1 of the table A Read off the corresponding output on the left Example Maximum output operation Natural gas G 20 NCV 9 45 kWh Sm3 Gas pressure at test point 1 B 11 0...

Page 13: ...lio se la sonda e l elettrodo sono correttamente posizionati come in C Separare quindi la testa di combustione dal resto del bruciatore fig B Allentare le 4 viti 3 e togliere il cofano 1 Sganciare lo...

Page 14: ...check through the blast tube opening to make sure that the flame sensor probe and the ignition electrode are correctly set in position as shown in C Now detach the combustion head from the burner fig...

Page 15: ...Dal diagramma C risulta che per questa poten zialit la regolazione dell aria va effettuata sulla tacca 3 come in fig B Continuando l esempio precedente a pag 12 si vede che per un bruciatore con poten...

Page 16: ...tion to 450 Mcal h circa 520 kW Example Maximum burner output 1370 Mcal h If we consult diagram C we find that for this output air must be adjusted using notch 3 as shown in fig B Continuing with the...

Page 17: ...iate P1 Pressione alla testa di combustione P2 Pressione a monte valvole regolatore P3 Pressione a monte del filtro L Rampa gas fornita a parte con il codice indicato in tab B L1 A cura dell installat...

Page 18: ...are compulsory for burners with maximum outputs of more than 1200 kW 9 Gasket 10 Standard issue burner gasket 11 Gas adjustment butterfly valve 12 Maximum gas pressure switch 13 Gas train burner adapt...

Page 19: ...atura elettrica MB Morsettiera bruciatore MV Motore ventilatore PA Pressostato aria PGM Pressostato gas di massima RT Rel termico S1 Interruttore per funzionamento MAN manuale AUT automatico OFF spent...

Page 20: ...Key to Layout A CMV Motor contactor F1 Protection against radio interfer ence LFL 1 3 Control box MB Burner terminal strip MV Fan motor PA Air pressure switch PGM Maximum gas pressure switch RT Therma...

Page 21: ...lo tenuta valvole gas avviene subito prima di ogni avviamento del bruciatore Fusibile e sezione cavi schemi B C vedi tab D Sezione non indicata 1 5 mm2 Legenda schemi B C IN Interruttore elettrico per...

Page 22: ...ol device LAYOUT C Electrical connection RS 190 M burner with VPS leak detection control device Gas valve leak detection control takes place immediately before every burner start up Fuses and cables c...

Page 23: ...esso NOTE Il bruciatore RS 190 M lascia la fabbrica previsto per alimentazione elettrica 400 V Se l alimen tazione 230 V cambiare il collegamento del motore da stella a triangolo e la taratura del rel...

Page 24: ...d be positioned to MAX Even if the scale of the thermal cut out does not include rated motor absorption at 400 V protec tion is still ensured in any case N B Burner RS 190 M leaves the factory preset...

Page 25: ...mo A bruciatore funzionante alla potenza MAX la farfalla del gas deve risultare tutta aperta 90 Camma II 0 Limita la rotazione verso il minimo A bruciatore spento la serranda dell aria e la far falla...

Page 26: ...e vari able profile cam and the gas butterfly valve The servomotor rotates through 130 degrees in 42 seconds Do not alter the factory setting for the 5 cams simply check that they are set as indicated...

Page 27: ...l accensione deve essere uguale o inferiore a 300 kW con ts 2 s 200 kW con ts 3 s Per misurare la potenza all accensione Scollegare la spina presa 7 A p 8 sul cavo della sonda di ionizzazione il bruci...

Page 28: ...r will fire and then go into lock out after the safety time has elapsed Perform 10 firings with consecutive lock outs On the meter read the quantity of gas burned This quantity must be equal to or low...

Page 29: ...viti successive Fare attenzione che la variazione del profilo della camma sia progressiva Spegnere il bruciatore agendo sull interruttore 1 A p 28 posizione OFF svincolare la camma 4 A dal servomotor...

Page 30: ...moteur en position de puissance MIN avec le bouton diminution de la puissance Pour le r glage ventuel de la came III surtout pour de l gers d placements on peut utiliser la clavette 10 B pr vue cet ef...

Page 31: ...ruciatore funzionante alla potenza MAX diminuire la pressione di regolazione girando lentamente in senso antiorario l apposita mano polina fino al blocco del bruciatore Girare quindi in senso orario l...

Page 32: ...erating at MAX output reduce the adjustment pressure by slowly turn ing the relative knob anticlockwise until the burner locks out Then turn the knob clockwise by 2 mbar and repeat burner firing If th...

Page 33: ...statI aria e gas di massima Se la temperatura o la pressione bassa per cui il telecomando TR chiuso il bruciatore aumenta progressivamente la potenza fino al valore MAX tratto C D Se poi la temperatur...

Page 34: ...tinue n anmoins v rifier la pr sence de la flamme et la position correcte des pressostats air et gaz maximum Si la temp rature ou la pressionsont basses et que par cons quent la t l commande TR est fe...

Page 35: ...verso sinistra il pulsante 2 B p 30 Bruciatore Controllare che non vi siano usure anomale o viti allentate nei cinematismi che comandano la serranda aria e la farfalla del gas Cos pure bloccate devon...

Page 36: ...it moves freely Now engage the cam again by moving the but ton 2 B p 30 to the left Burner Check for excess wear or loose screws in the mechanisms controlling the air gate valve and the gas butterfly...

Page 37: ...tti 10 8 apparecchiatura Superata la preventilazione ed il tempo di sicurezza il bruciatore va in blocco senza apparizione di fiamma 23 L elettrovalvola VR fa passare poco gas Aumentarlo 24 L elettrov...

Page 38: ...altung des Brenners nach der Vorbel ftung und der Sicherheitszeit ohne Flammenbil dung 23 Ungen gender Gasflu durch das Magnetventil VR Steigern 24 Magnetventil VR bzw VS ffnet nicht Spule oder Gleich...

Page 39: ...ervomotor control box terminals 10 8 After pre purge and safety time the burner goes to lock out and the flame does not appear 23 The solenoid VR allows little gas through Increase 24 Solenoid valves...

Page 40: ...lation et le temps de s curit le br leur se bloque sans apparition de flamme 23 Electrovanne VR fait passer peu de gaz Augmenter 24 L lectrovanne VR ou VS ne s ouvre pas Remplacer bobinage ou panneau...

Reviews: