SpaceLogger
®
.S10
User Manual
©2012-13 Richard Paul Russell Limited, New Harbour Building, Bath Road, Lymington SO41 3SE United Kingdom
Tel +44 (0) 1590 679755 Fax +44 (0) 1590 688577 e-mail [email protected] web www.r-p-r.co.uk
- 14 -
017SL167/3 04/09/13
5.10
To Select a Logging Interval
By default, the SpaceLogger.S10 will record every sample output by the attached sensor.
If an alternative logging interval is required, the SpaceLogger.S10 may be set to record at a less
frequent sample rate by using the following SETUP.TXT command line:
RATE=r
Where r is the time in seconds between sampling for the STX condition, as an integer.
Note:
r = 0 to 60
r should be set to a value greater than the sensor output interval or 0
If r = 0, every sample received by the SpaceLogger will be recorded – i.e. the
SpaceLogger looks for the next STX condition immediately after the ETX
condition (or ETX2 condition, if enabled) is detected.
5.11
To Record Data to a Single Log File
SpaceLogger.S10 creates a folder
DATA
on the SD card root folder. Data files are written to this
folder. By default, a new file is generated at the start of each day.
If preferred, rather than the SpaceLogger.S10 creating daily files, all data may be set to record to
one continuous log file. This is enabled using the following SETUP.TXT command line:
SINGLEFILE=f
Where f = Y or N
If f =
Y
, data is stored in a single log file
If f =
N
, data is stored in daily files