PERATION OF THE OPERATING ACCESSORIES

O

PENING BUTTON (COM-OPEN) with timer function

When  the  gate  is  standstill,  the  button  operates  the  opening  mode.  If
you push this button when the gate is on closure, it opens again. 

T

IMER FUNCTION OF THE OPENING BUTTON

This function is useful In the rush hours, when vehicle traffic is slow  and
high  (e.g.  entry/exit  of  workers,  emergencies  In  residential  or  parking
areas and, temporary, for removals).

APPLICATIONS

By  connecting  a  switch  and/or  a  daily/weekly  timer  (in  place  or  in
parallel  with  the  opening  button  N.O.  “COM-OPEN”),  it  is  possible  to
open the automation or to keep It open, as long as the switch is on or
the timer is activated.
When the automation is open, all operating functions are inhibited.
If  the  automatic  closing  is  enabled  by  releasing  the  switch,  the  gate
immediately closes; if not, you need to operate a command.

C

LOSING BUTTON (COM-CLOSE)

When the gate is standstill, it operates the closing.

J

OGGING OPERATION BUTTON (COM-K BUTTON)

DIP5 - OFF =>

It cyclically commands open-stop-close-stop-open-etc.

DIP5 - ON =>

It  opens  the  gate  when  this  Is  closed.  If  it  is  operated
while the gate Is opening, It has no effect. If it is operated
when the gate is open, it closes the gate. If it is operated
while the gate is closing, it opens the gate again.

R

ADIO TRANSMITTER

DIP4 - OFF =>

It cyclically commands open-stop-close-stop-open-etc.

DIP4 - ON =>

It  opens  the  gate  when  this  is  closed.  If  it  is  operated
while the gate Is opening, It has no effect. If it is operated
when the gate is open, it closes. If it is operated while the
gate is closing, it opens the gate again.

A

UTOMATIC  CLOSING  FOR  COMPLETE  OR  PEDESTRIAN

OPENING

The  pausing  time  before  the  automatic  closing  for  both,  complete  or
pedestrian opening, is set during the “D - Time Programming”. In both
cases  the  maximum  pausing  time  available  is  5  minutes.  Pause  time
can be enabled or disabled by DIP3 (ON enabled).

O

PERATION AFTER BLACK-OUT

When mains electrical power is restored press the opening button (K,
OPEN, radio).
The  gate  will  open.  Let  the  gate  close  itself  with  automatic  closure  or
wait  that  the  flasher  stops  blink  and  then  command  the  closing
movement.  This  operation  is  valid  to  obtain  the  leaves  position
readjustment. During this phase all safety devices are active.

S

AFETY ACCESSORIES OPERATION

S

AFETY ENCODER (only for K PLUS)

It  must  act  as  a  security  in  opening  and  closing,  with  movement
inversion in case of collision.
DIP 7 (ON) operates the motor with encoder.

In case of Encoder failure (due to a failure In the power supply, disconnected
wires, broken or defective Encoder disk), the gate doesn’t work.
If  after  the  first  impact,  the  gate  reverses  the  movement  but  it  finds
another obstacle, the gate reverses again for only one second and then
stops. 

The buzzer sound to for 5 minutes, to indicate the state of

alarm, and the blinker blinks for 1 minute. 

During or after the 5 minutes, when the buzzer sounds, you can make
the gate work again just pressing the operating button you want.

P

HOTOCELL 1 (COM-PHOT 1))

DIP 6 - OFF => 

The  gate  does  not  open  if  there  is  an  obstacle  within
the  photocells  range  of  action.  During  operation,
photocells work both when the gate opens (by starting
the opening movement again after half a second time),
and when it closes (by starting the reverse movement
after one second time).

DIP 6 - ON =>

If  there  is  an  obstacle  within  the  photocells  range  of
action  when  the  gate  is  closed  and  its  opening  is
commanded,  the  gate  opens  (during  its  opening,
photocells do not work). Photocells work only while the
gate  is  closing  (by  starting  its  reverse  movement  after
one second, even if they are still engaged).$

S

TOP BUTTON (COM-STOP)

The STOP button stops the gate during any operation. 

If you push it when the gate is totally open (or partly open, by using the
pedestrian  command),  this  button  temporary  excludes  the  automatic
closing  (if  selected  by  DIP3). Than  it  is  necessary  to  operate  another
command to make the gate close again.
The  automatic  closing  function  Is  enabled  again  with  the  following
operating cycle (if selected by DIP3).

B

LINKER

N.B.: This  electric  board  can  supply  power  ONLY TO  BLINKERS

WITH  (Code  ACG7059)  BLINKING  CIRCUIT,  with  max.  40W
lamps.

PRE-BLINKING FUNCTION:
- With DIP8  on OFF

=> the motor, the blinker and the buzzer start at

the same time.

-  With DIP 8 on ON

=> the  blinker  and  the  buzzer  start  3  seconds

before the motor.

B

UZZER (Optional) - PAY ATTENTION TO THE POLARITY -

Current as supplied for buzzer operation 200 mA 12Vdc.

The buzzer emits an intermittent sound signal during opening and
closing  cycles.  When  safety  devices  are  operated  (alarm),  the
intermittence frequency of this sound signal Increases.

W

ARNING LIGHT OF GATE OPEN  (COM-SIGNAL)

Its function is to signal when the gate Is open, partly open or not totally
closed anyway. It turns off only when the gate Is totally closed.
This warning signal is not enabled during the programming procedures.

N.B.:

If you overuse the push button panels or the lamps, the
control  board  logic  system  may  be  compromised,
resulting into a possible operation block.

Summary of Contents for K400 230V

Page 1: ...EUTCH pag ESPANOL pag OPERATORE IRREVERSIBILE PER CANCELLI SCORREVOLI OPERATEUR IRREVERSIBLE POUR PORTAILS COULISSANTES IRREVERSIBLE OPERATOR FOR SLIDING GATES SELBSTHEMMENDER TORANTRIEB F R SCHIEBETO...

Page 2: ...ER SOIGNEUSEMENT CES INSTRUCTIONS 1 Si la centrale lectrique ne dispose d aucun interrupteur il faut en installer un de type magn tothermique en amont de cette derni re omnipolaire avec ouverture mini...

Page 3: ...SAFETY OF THE PEOPLE IT IS IMPORTANT TO FOLLOW ALL THE INSTRUCTIONS INSTALLATIONSVORSCHRIFTEN BEACHTET WERDEN 1 Wenn nicht bereits an der elektrischen Schaltzentrale vorgesehen muss vor der Schaltzen...

Page 4: ...stema respetando las normas y las leyes vigentes SEGUIR TODAS LAS INSTRUCCIONES DE INSTALACI N 1 Este manual de instrucciones est exclusivamente dirigido a personal especializado que conozca los crite...

Page 5: ...lettrica per un efficace chiusura Il motore protetto da una sonda termica che in caso di utilizzo prolungato interrompe momentaneamente il movimento I I Misure in mm 1 Kg 400 m s 0 155 0 18 N 500 4 23...

Page 6: ...tolto l alimentazione elettrica al motore Per poter agire manualmente sul cancello sufficiente inserire l apposita chiave e ruotarla 3 volte in senso antiorario 4 Per poter eseguire in modo sicuro la...

Page 7: ...FISSAGGIO FINECORSA Per determinare la corsa della parte mobile si devono posizionare due camme alle estremit della cremagliera 7 La regolazione della corsa di apertura e chiusura si ottiene spostando...

Page 8: ...I I COLLEGAMENTI ELETTRICI centralina KS cod BC07050...

Page 9: ...ti Contatto fotocellule NC Connettore per logica scheda INVERTER opzionale Contatto pulsante stop NC Contatto pulsante di apertura NA Contatto pulsante di chiusura NA Contatto impulso singolo NA Alime...

Page 10: ...ttere il DIP1 in posizione ON Il led DL5 inizia a lampeggiare 3 Premere e mantenere premuto il pulsante PROG ora il movimento eseguito ad uomo presente apre stop chiude stop apre ecc Il LED ROSSO DL7...

Page 11: ...o di agire come sicurezza sia in apertura che in chiusura con inversione del moto in caso di impatto Il funzionamento del motore con Encoder abilitato dal DIP 7 ON In caso di mancato funzionamento del...

Page 12: ...ura NC 12 Comune SEGNALAZIONI LED SCHEDA EXPANDER D2 segnalazione contatto fotocellula 2 D3 segnalazione contatto comando pedonale D4 segnalazione contatto costa D5 Presenza tensione N B Per un corret...

Page 13: ...R a bordo della scheda EXPANDER Il rel verr attivato ad ogni apertura o chiusura GESTIONE SEMAFORO A cancello chiuso il semaforo spento All apertura si accende la luce rossa 3 4 A cancello aperto si a...

Page 14: ...ecoman ANTENNA SPARK 91 cod ACG5454 ANTENNA SPARK 433 cod ACG5252 LAMPEGGIATORE SPARK con scheda intermittente incorporata cod ACG7059 FIT SYNCRO FOTOCELLULE FIT SYNCRO DA PARETE cod ACG8026 Portata s...

Page 15: ...n type de serrure lectrique pour une fermeture efficace Le moteur est prot g par une sonde thermique qui interrompt momentan ment le mouvement en cas de non utilisation prolong e Mesures en mm 1 Kg 40...

Page 16: ...tre effectu e qu apr s avoir mis le moteur hors tension Afin de pouvoir agir manuellement sur le portail il suffit d introduire la cl destin e cet effet et de la faire tourner 3 fois dans le sens cont...

Page 17: ...ositionner deux cames sur les extr mit s de la cr maill re 7 Pour proc der au r glage de la course d ouverture et de fermeture il suffit de d placer les cames sur les crans de la cr maill re Pour bloq...

Page 18: ...F F BRANCHEMENTS LECTRIQUES coffret electronique KS cod BC07050...

Page 19: ...tacts Contact photocellules NF Connecteur pour logique carte INVERTER option Contact poussoir de stop NF Contact poussoir d ouverture NO Contact poussoir de fermeture NO Contact impulsion simple NO Al...

Page 20: ...portail en position interm diaire 2 Placer le DIP1 sur ON Le voyant lumineux DL5 commencera clignoter 3 Appuyer sans rel cher sur la touche PROG d s pr sent le mouvement est effectu en mode homme mort...

Page 21: ...Pendant cette phase les s curit s sont actives FONCTIONNEMENT DES ACCESSOIRES DE S CURIT ENCODEUR DE S CURIT KPLUS A la capacit d agir comme une s curit aussi bien en ouverture qu en fermeture avec in...

Page 22: ...es en tension dangereuse Toutes les entr es sont g r es par un circuit int gr programm pour ex cuter un auto contr le chaque mise en marche FONCTIONS SUPPL MENTAIRES AVEC CARTE EXPANDER code ACG5470 E...

Page 23: ...on ult rieure apr s 2 secondes pour ensuite ex cuter une autre petite inversion et donc signaler l alarme de cordon en panne ou engag contact NO si le cordon reste engag contact NO aucun mouvement n e...

Page 24: ...tall N B Veiller ce que le fil central du c ble n entre pas en contact avec l enveloppe ext rieure en cuivre dans le cas contraire le fonctionnement de l antenne serait nul L antenne doit tre install...

Page 25: ...de ACS9001 CR MAILL RE MOD 4 acier trait cataphor se avec corni re en barre de 2ml code ACS9050 Id al pour les portails jusqu 2200 Kg PLAQUE CIMENTER code ACG8107 OLIVE EN NYLON code ACG4010 Appliquer...

Page 26: ...any electric lock for an effective closing of the gate The motor is protected by an heat probe that temporary interrupts the operating cycle in case of prolonged use Measurements in mm inch 1 Kg 400 m...

Page 27: ...e gate you just need to insert the fitting key and rotate it 3 times counterclockwise 4 In order to carry out the manual operation of the gate leaf the followings must be checked That the gate is endo...

Page 28: ...NG In order to determine the gate travel length place two cams at the ends of the rack 7 Move the cams on the rack teeth to adjust their opening and closing travel To fix the cams to the rack tighten...

Page 29: ...G G B B ELECTRIC CONNECTIONS electric board KS code BC07050...

Page 30: ...logic of the INVERTER card optional Contact of the stop button NC Contact of the opening button NO Contact of the closing button NO Contact of a single impulse NO 24 Vac accessories power supply Warni...

Page 31: ...position The LED DL5 starts blinking 3 Press the PROG button and hold it the gate now is controlled in a dead man mode open stop close stop open THE RED LED DL7 CLOSE turns on and the gate starts clos...

Page 32: ...ion in case of collision DIP 7 ON operates the motor with encoder In case of Encoder failure due to a failure In the power supply disconnected wires broken or defective Encoder disk the gate doesn t w...

Page 33: ...BUTTON 10 12 This command operates the partial opening of the gate and Its closing When the gate Is partly open it is not possible to operate its total opening using the pedestrian command It is first...

Page 34: ...the traffic light turned off TRAFFIC LIGHT CONTROL When the gate is completely closed both the traffic lights are turned OFF During the opening the red light 3 4 turns ON When the gate si completly o...

Page 35: ...ou can fit many couples close together thanks to the synchronising circuit Add the SYNCRO TRANSMITTER code ACG8028 for more than 2 photocells couples up to 4 COUPLE OF BUILT IN BOXES FOR THE FIT SYNCR...

Page 36: ...sket The gasket is fitted Motor ready Close the case FINAL OPERATION The gasket shall be fitted only at the end of the installation before you mount the case follows from page 35 NYLON OLIVE code ACG4...

Page 37: ...en Verriegelung kein elektrisches Sicherheitsschloss Der Motor wird durch eine thermische Sonde gesch tzt die im Fall eines langen Einsatzes momentan die Bewegung unterbricht Abmessungen in mm 1 Kg 40...

Page 38: ...darf erst nach dem Abschalten der elektrischen Motorstromversorgung erfolgen Um das Tor manuell richtig zu pruefen muessen folgende Punkte beachtet werden Das Tor muss einen geeigneten Griff haben Di...

Page 39: ...beenden m ssen zwei Nocken an den Enden der Zahnstange positioniert werden 7 Die Regulierung des ffnungs und Schlie laufes wird erhalten indem diese entlang der Zahnstangenz hne verschoben werden Um d...

Page 40: ...D D ELEKTROANSCHL SSE elektronische steuerung KS code BC07050...

Page 41: ...e Fotozellen Kontakt NC Verbinder f r die Logik der INVERTER Karte optional Kontakt Taste Stop NC Kontakt Taste zum ffnen NO Kontakt Taste zum Schlie en NO Kontakt Einzelimpuls NO Zubeh rversorgung 24...

Page 42: ...Personen Pr senz ffnen Stop schlie en Stop ffnen etc LED ROT DL7 CLOSE erleuchtet und das Tor muss sich nun schlie en geschieht dies nicht muss die Taste PROG losgelassen und die Verbindungskabel des...

Page 43: ...nur f r K PLUS Es mu als eine Sicherheit in der ffnung und im Schlie en mit Bewegung Umstellung dienen falls vom Zusammensto Der Betrieb des Motors mit Encoder wird mit dem DIP7 ON zugelassen Falls d...

Page 44: ...G5470 DIE KARTE EXPANDER NUR BEI ABGESCHALTETEM STROM EINSCHIEBEN LEGENDE TR Trimmer zur Einstellung der Hilfslichtdauer 1 2 Versorgung 24Vdc f r Fotozellen Fotokontaktleisten usw 3 4 Ampelkontakt 1 5...

Page 45: ...iert damit den Alarmzustand der nicht einsatzf higen schadhaften oder anders eingesetzten Rippe Kontakt NO Bleibt die Rippe weiterhin eingesetzt Kontakt NO kann keine andere Bewegungserlaubnis erfolge...

Page 46: ...te Antenne montiert werden Anmerkung Besonders muss darauf geachtet werden dass das Zentralkabel der Leitung nicht mit der externen Kupferumwicklung in Kontakt kommt da dies die Funktion der Antenne a...

Page 47: ...doppeltem Sicherheitskontakt Abmessungen k nnen nach Wunsch geschnitten werden BEFESTIGUNGSSET f r schwere Tore bis 600kg Code ACG4655 NYLON ZAHNRAD MOD 4 mit verzinkter Ecke als Stange zu 1m Ideal f...

Page 48: ...LHITGREASE EP GR 2 10 5Kg db 70 C 10 55 C IP 44 1 Operador K 2 Fotoc lulas externas 3 Cremallera M dulo 4 4 Interruptor de llave 5 Antena de radio 6 Intermitente 7 Limitadores de recorrido leva 8 Nerv...

Page 49: ...ntaci n el ctrica al motor Para poder abrir manualmente la cancela en el caso de que faltase la corriente el ctrica con introducir la llave y girarla 3 veces en sentido opuesto a las agujas del reloj...

Page 50: ...a determinar el recorrido de la parte m vil se tiene que colocar dos limitadores de recorrido en los extremos de la cremallera 7 La regulaci n de la abertura y el cierre se obtiene desplazando la mism...

Page 51: ...E E S S CONEXIONES EL CTRICAS panel electronico KS c d BC07052...

Page 52: ...s Contacto fotoc lulas NC Conector para l gica tarjeta INVERTER opcional Contacto pulsador stop NC Contacto pulsador de abertura NA Contacto pulsador de cierre NA Contacto impulso nico NA Alimentaci n...

Page 53: ...s 1 Despu s de haber regulado los finales de carrera el ctricos posicionar la cancela a mitad de carrera por medio del seguro manual 2 Poner el DIP1 en posici n ON el led DL5 inicia a parpadear 3 Pres...

Page 54: ...n activos FUNCIONAMIENTO DE LOS ACCESORIOS DE SEGURIDAD ENCODER DE SEGURIDAD K PLUS Es una seguridad sea en apertura que en cierre con la inversi n del movimiento en caso de colisi n El funcionamient...

Page 55: ...ica intermitente En caso de intervenci n de los sistemas de seguridad alarma dicha se al ac stica aumenta la frecuencia de la intermitencia PILOTO DE INDICACI N DE VERJA ABIERTA COM SIGNAL Su funci n...

Page 56: ...aci n FOTOC LULA 2 9 12 Durante la abertura si se intercepta al final de la interposici n invierte el cierre Durante el cierre si se intercepta al final de la interposici n invierte la abertura Esta f...

Page 57: ...cionamiento de la antena Instale la antena verticalmente y de tal manera el mando a distancia puede alcanzarla ANTENA SPARK 91 c d ACG5454 ANTENA SPARK 433 c d ACG5252 FIT SYNCRO FOTOC LULAS FIT SYNCR...

Page 58: ...OD 4 en metal con tratamiento de CATAFORESIS con angular in barras de 2mt 6 56 feet c d ACS9050 Ideal para cancelas con peso hasta 2200Kg CREMALLERA MOD 4 DE NYLON con angular galvanizado en barras de...

Page 59: ...utres l ments Aussi rentre t il dans le champ d application de l art 4 paragraphe 2 de la Directive machines 98 37 CEE et de ses modifications successives Sa mise en service est interdite avant que l...

Page 60: ...DOLO BS ITALY Via Matteotti 162 Telefono 39 030 2135811 Telefax 39 030 21358279 21358278 http www ribind it email ribind ribind it automatismi per cancelli automatic entry systems K400 230V Cod CVA173...

Reviews: