MODE 2 – TIMED (DIP 7 ON)

1 - The gate must be fully closed.
2 - Position DIP 2 to ON => LED L9 will emit brief flashes.

3 - Press PROG. button

=> M1 opens.

4 - Upon reaching the mechanical stop on opening, 

after one second press the PROG.

button

=> M1 stops and M2 opens.

5 - Upon reaching the mechanical stop on opening => 

after 1 second press the PROG.

button

=> M2 stops => At the same time countdown begins of the waiting time before

automatic closing (max 5 minutes).

6 - Press the PROG. button

=> Countdown of the waiting time before automatic closing

stops and M2 closes.

7 - Press the PROG. button 

=> M1 closes thus establishing the interval between M2 and

M1.  At  the  same  time  LED  L9  will  stop  flashing,  signalling  exit  from  the  learning
process. From this moment onwards the safety devices or other controls for the gate
will work normally (reversal, stops, alarms, etc....).

8 - Once countdown of the time has finished the gate will stop.

9 - AT THE END OF PROGRAMMING RETURN DIP 2 TO OFF.

D – PROGRAMMING OF TIMING FOR 1 MOTOR (M1) (#)

NOTE: TO OPERATE JUST ONE MOTOR CUT JUMPER JP3.

PROGRAMMING CAN BE CARRIED OUT IN TWO WAYS.

MODE 3 – WITH CURRENT SENSOR (DIP 7 OFF)

The gate must be fully closed.

1 - Position DIP 2 to ON

=> LED L9 will emit brief flashes.

2 - Press  PROG.  button 

=>  M1  open.  Upon  reaching  the  mechanical  stop  for  opening,

the CURRENT SENSOR stops M1 (with memorization of the time). At the same time
the  countdown  of  the  waiting  time  before  automatic  closing  is  activated  (max  5
minutes).

3 - Press the PROG. button

=> Countdown of the waiting time before automatic closing

stops and M1 closes. At the same time LED L9 will stop flashing, signalling exit from
the learning process. From this moment onwards the safety devices or other controls
for the gate will work normally (reversal, stops, alarms, etc....).

Upon reaching full closure the gate stops via the current sensor.

4 - AT THE END OF PROGRAMMING RETURN DIP 2 TO OFF.

MODE 4 – TIMED (DIP 7 ON)

The gate must be fully closed.

1 - Position DIP 2 to ON

=> LED L9 will emit brief flashes.

2 - Press PROG. button

=> M1 opens.

3 - Upon reaching the mechanical stop on opening, 

after one second press the PROG.

button

=>  M1  stops    and  countdown  begins  of  the  waiting  time  before  automatic

closing (max 5 minutes).

4 - Press the PROG. button 

=> Countdown of the waiting time before automatic closing

stops and M1 closes. At the same time LED L9 will stop flashing, signalling exit from
the learning process. From this moment onwards the safety devices or other controls
for the gate will work normally (reversal, stops, alarms, etc....).

Once the countdown has finished the gate closes.

5 - AT THE END OF PROGRAMMING RETURN DIP 2 TO OFF.

(#)  DURING  PROGRAMMING  THE  SAFETY  DEVICES  ARE  ACTIVE  AND  THEIR

INTERVENTION  WILL  STOP  PROGRAMMING  (LED  L9  STOPS  FLASHING  AND
REMAINS FULLY ON). IN ORDER TO REPEAT PROGRAMMING POSITION DIP 2 TO
OFF,  CLOSE  THE  GATE  USING  THE  “CONTROL  FOR  MOTOR  ROTATION
DIRECTION” PROCEDURE AND REPEAT THE CHOSEN PROGRAMMING.

E – RADIO CODE LEARNING PROCEDURE EXCLUSIVELY FOR

CRX MODELS (MAX 32 CODES)

To be carried out with the gate closed.

1 - Position DIP 1 to ON and then DIP 2 to ON 

=> Programming LED L9 will flash with

the frequency of 1 sec. ON and 1 sec. OFF for 10 seconds, which is the time available
for programming the code.

2 - Press the button on the remote control

(usually channel A) within the 10 seconds

set.  If  the  remote  control  is  memorized  correctly  green  LED  L10  emits  a  flash.  The
code programming time is automatically renewed to allow for the memorization of the
next remote control.

3 - To  end  programming  allow  10  seconds  to  pass., 

or  press  the  PROG.  button  for  a

moment

=> LED L9 and LED L10 will remain fully on.

4 - Return DIP 1 to OFF and DIP 2 to OFF,

LED L9 and LED L10 will go out.

PROCEDURE TO CANCEL RADIO CODES
1 - Position DIP 1 to ON and then DIP 2 to ON.

Programming LED L9 will flash with the

frequency of 1 sec. ON and 1 sec. OFF for 10 sec. 

2 - During  these  10  seconds  => 

press  the  PROG.  button  and  keep  it  pressed  for  5

seconds

=> cancellation of the memory will be indicated by two flashes of green LED

L10. Following which programming LED L9 will remain active and it will be possible to
insert new codes using the procedure described above.

3 - At the end return DIP1 and DIP 2 to OFF, LED L9 and LED L10 will go out.

FULL MEMORY SIGNAL
1 - Position  DIP  1  -  ON  and  then  DIP  2  –ON. 

Green  LED  L10  flashes  six  times,

indicating  that  the  memory  is  full.  Following  which,  programming  LED  L9  remains
active for 10 seconds, allowing for the complete cancellation of all codes if necessary.

2 - At the end return DIP1 and DIP 2 to OFF,

LED L9 and LED L10 will go out.

FUNCTIONING OF CONTROL ACCESSORIES

STEP BY STEP CONTROL BUTTON (COM-K BUTTON)

DIP 6 - ON =>

Perform the cyclic command open-stop-close-stop-open-etc.

DIP 6 - OFF =>

Perform opening with the gate closed. If activated during opening it has no
effect.  If  activated  with  the  gate  open,  it  closes  it.  If  activated  during
closing it will re-open.

CLOCK FUNCTION (ONLY WITH DIP 6 OFF)

This  function  is  useful  during  rush  hours,  when  traffic  is  slow  (e.g.  entrance/exit  of
workers,  emergencies  in  residential  areas  or  car  parks  and,  temporarily,  for  removal
vans).

METHOD OF APPLICATION

By  connecting  a  switch  and/or  a  daily/weekly  clock    (instead  of,  or  parallel  to  the  N.A.
opening button “COM-K-BUTTON”), it is possible to open, and keep open, the automation
until the switch is pressed or whilst the clock is active.
Once the automation is open all the control functions are blocked.
If automatic closing is activated, upon releasing the switch, or when the time established
has lapsed, immediate closure of the automation will occur, otherwise it will be necessary
to give a command.

REMOTE CONTROL 

DIP 6 - ON =>

Perform the cyclic command open-stop-close-stop-open-etc

DIP 6 - OFF =>

Perform opening with the gate closed. If activated during opening it has no
effect. If activated with the gate fully open, it closes it. If activated during
closing it will re-open. 

AUTOMATIC CLOSURE

The  waiting  times  before  the  gate  closes  automatically  are  recorded  during  the
programming of timing.
The maximum waiting time is 5 minutes.
The waiting time can be activated or deactivated using DIP 3 (ON - active).

ELECTRIC LOCK (LOCK - A +)

Place DIP 8 to ON to enable the command for the electric lock on opening.

ELECTRIC LOCK RELEASE ON OPENING

Place DIP 9 to ON to enable the release of the electric lock on opening (provided that DIP
8 is to ON).
With the gate closed, if you press an opening command, the gate will perform the closing
manoeuvre for 0.5s (the current sensors in this phase are not enabled) and at the same
time the electric lock is activated (followed by a pause of 0.5s and then the opening of the
gate).

WING RELEASE FACILITY

With the electric lock release activated (DIP 9 to ON), once the gate has closed a reversal
manoeuvre , with a fixed time of 0.2s will be performed to facilitate manual release (the
current sensors in this phase are not enabled).

ELECTRIC LOCK COUPLING

Put DIP 10 to ON to enable electric lock coupling on closing, once closed the motors are
controlled  for  0.5s  with  full  voltage  to  guarantee  the  coupling  of  the  lock  (the  current
sensors in this phase are not enabled).

FUNCTIONING AFTER A BLACKOUT (WITHOUT BATTERIES)

Once voltage returns we recommend that the gate be fully opened. Allow the gate to close
by itself with automatic closure or wait for the flashing light to stop flashing before giving
the command to close.
This operation will allow the gate to realign itself. In fact, if during the blackout the motors
were released and moved from the normal closing position, the first manoeuvre when the
power supply returns must be complete.
During this phase the safety devices are active.

PHOTOCELL 1 (COM-PHOT)

If DIP 4 to OFF -

If  an  obstacle  blocks  the  photocell  beam  whilst  the  gate  is  closed,  the
gate  will  not  open.  During  functioning  the  photocells  intervene  both  on
opening (with reactivation of movement on opening after half a second),
and on closing (with reactivation of reversal after a second).

If DIP 4 to ON -

If  an  obstacle  blocks  the  photocell  beam  whilst  the  gate  is  closed,  the
gate  will  open  (during  opening  the  photocells  do  not  intervene).  The

Pag. 18 di 28

E

N

G

L

I

S

H

Summary of Contents for ABK0024

Page 1: ...m Auswirkung sensoren Pag 1 di 28 I F GB D ISTRUZIONI DI MONTAGGIO INSTRUCTION POUR LE MONTAGE ASSEMBLY INSTRUCTIONS MONTAGEANWEISUNGEN K2 24V Mod K2 24V cod ABK0024 K2 24V CRX cod ABK0025 ATTENZIONE Ricordarsi di regolare i sensori di impatto vedi paragrafo C pagina 5 ATTENTION Rappelez vous d ajuster les capteurs d impact voir le paragraphe C de la page 11 ATTENTION Remember to adjust the impact...

Page 2: ...ottemperanza alle norme ed alle leggi vigenti IMPORTANTES INSTRUCTIONS DE SECURITE POUR L INSTALLATION ATTENTION UNE INSTALLATION NON CORRECTE PEUT CAUSER DE GRAVES DOMMAGES SUIVRE TOUTES LES INSTRUCTIONS D INSTALLATION 1 Ce livret d instructions est adressé exclusivement à un personnel spécialisé qui connaît les critères de construction et les dispositifs de protection contre les accidents concer...

Page 3: ...TION ACHTUNG EINE UNKORREKTE INSTALLATION KANN SCHWERE SCHÄDEN VERURSACHEN ALLE INSTALLATIONSANLEITUNGEN BEFOLGEN 1 Diese Betriebsanleitung dient ausschließlich dem Fachpersonal welches die Konstruktionskriterien und die Sicherheits Vorschriften gegen Unfälle für Tore Türen und automatische Tore Kennt geltende Normen und Gesetze beachten und befolgen 2 Der Monteur muss dem Endkunde eine Betriebsan...

Page 4: ...I T A L I A N O Pag 4 di 28 COLLEGAMENTI ELETTRICI K2 24V Cod BC07059 K2 24V CRX Cod BC07058 ...

Page 5: ...E MOTORE 1 RL3 RELE CHIUDE MOTORE 2 RL4 RELE APRE MOTORE 2 OMNIFET Q1 OMNIFET DI POTENZA CHE COMANDA IL MOTORE 1 SIA IN APERTURA CHE IN CHIUSURA Q2 OMNIFET DI POTENZA CHE COMANDA IL MOTORE 2 SIA IN APERTURA CHE IN CHIUSURA FUSIBILI F 1 6A FUSIBILE DI PROTEZIONE TRASFORMATORE esterno alla scheda K2 24V F1 4A FUSIBILE DI PROTEZIONE ACCESSORI F2 4A FUSIBILE DI PROTEZIONE MOTORE 1 F3 4A FUSIBILE DI PR...

Page 6: ...2 su ON Il led L9 di programmazione lampeggerà con frequenza di 1 sec ON e 1 sec OFF per 10 sec 2 Durante i 10 secondi premere e mantenere premuto il pulsante PROG per 5 secondi la cancellazione della memoria viene segnalata da due lampeggi del led verde L10 In seguito il led L9 di programmazione rimane attivo ed è possibile inserire nuovi codici come da procedura sopra descritta 3 Al termine rime...

Page 7: ...ssibile ristabilire il funzionamento del cancello premendo un qualsiasi pulsante di comando SPIA DI SEGNALAZIONE CANCELLO APERTO COM SIGNAL Ha il compito di segnalare gli stati di cancello aperto parzialmente aperto o comunque non chiuso totalmente Solo a cancello completamente chiuso si spegne Durante la programmazione questa segnalazione é attiva N B Max 3 W Se si eccede con le pulsantiere o con...

Page 8: ...atteria alla centralina con mancanza di tensione di rete il funzionamento del cancello viene garantito fino ad un livello di carica di circa 20V dopo di che subentra una segnalazione data dalla scheda di ricarica alla centralina che blocca il cancello e fa lampeggiare la spia stato batteria Al ritorno della tensione di rete si consiglia di far aprire completamente il cancello Lasciate che il cance...

Page 9: ...COSTOLA MECCANICA L 2MT cod ACG3010 Con doppio contatto di sicurezza e tagliabile a misura Pag 11 di 28 I T A L I A N O ...

Page 10: ...BRANCHEMENTS ÉLECTRIQUES Pag 10 di 28 K2 24V Code BC07059 K2 24V CRX Code BC07058 F R A N Ç A I S E ...

Page 11: ...RL3 RELAIS FERME MOTEUR 2 RL4 RELAIS OUVRE MOTEUR 2 OMNIFET Q1 OMNIFET DE PUISSANCE QUI COMMANDE LE MOTEUR 1 AUSSI BIEN EN OUVERTURE QU EN FERMETURE Q2 OMNIFET DE PUISSANCE QUI COMMANDE LE MOTEUR 2 AUSSI BIEN EN OUVERTURE QU EN FERMETURE FUSIBLES F 1 6A FUSIBLE DE PROTECTION TRANSFORMATEUR externe à la fiche K2 24V F1 4A FUSIBLE DE PROTECTION ACCESSOIRES F2 4A FUSIBLE DE PROTECTION MOTEUR 1 F3 4A ...

Page 12: ... OFF le led L9 et le led L10 s éteignent PROCEDURE D EFFACEMENT CODES RADIO 1 Positionner le DIP 1 sur ON et ensuite le DIP 2 sur ON Le led L9 de programmation clignotera à la fréquence de 1 sec ON et 1 sec OFF pendant 10 sec 2 Pendant les 10 secondes appuyer et maintenir appuyé le bouton PROG pendant 5 secondes l effacement de la mémoire est signalée par deux clignotements du led vert L10 Ensuite...

Page 13: ...nute Durant ou après les 5 minutes d alarme sonore buzzer il est possible de rétablir le fonctionnement du portail en appuyant sur un bouton de commande quelconque VOYANT DE SIGNALISATION PORTAIL OUVERT COM SIGNAL Il a la tâche de signaler les états du portail ouvert partiellement ouvert ou de toute façon non fermé en totalité Il s éteint seulement lorsque le portail est complètement fermé Durant ...

Page 14: ...URANT AVEC BATTERIES Si des batteries sont connectées à la centrale par manque de tension de réseau le fonctionnement du portail est garanti jusqu à un niveau de charge d environ 20V après quoi une signalisation donnée par la fiche de recharge à la centrale interviendra qui bloquera le portail et fera clignoter le voyant d état batterie Au retour du courant nous conseillons de faire s ouvrir compl...

Page 15: ...Pag 15 di 28 F R A N Ç A I S E CORDON MÉCANIQUE L 2MT code ACG3010 Avec double contact de sûreté et pouvant être coupée sur mesure ...

Page 16: ...Pag 16 di 28 K2 24V Code BC07059 K2 24V CRX Code BC07058 ELECTRIC CONNECTIONS E N G L I S H ...

Page 17: ...2 RL4 RELAY OPEN MOTOR 2 OMNIFET Q1 POWER OMNIFET THAT CONTROLS MOTOR 1 BOTH ON OPENING AND ON CLOSING Q2 POWER OMNIFET THAT CONTROLS MOTOR 2 BOTH ON OPENING AND ON CLOSING FUSES F 1 6A TRANSFORMER PROTECTION FUSE external to card K2 24V F1 4A PROTECTION FUSE FOR ACCESSORIES F2 4A PROTECTION FUSE FOR MOTOR 1 F3 4A PROTECTION FUSE FOR MOTOR 2 C CONTROL FOR MOTOR ROTATION DIRECTION AND CALIBRATION O...

Page 18: ... by two flashes of green LED L10 Following which programming LED L9 will remain active and it will be possible to insert new codes using the procedure described above 3 At the end return DIP1 and DIP 2 to OFF LED L9 and LED L10 will go out FULL MEMORY SIGNAL 1 Position DIP 1 ON and then DIP 2 ON Green LED L10 flashes six times indicating that the memory is full Following which programming LED L9 r...

Page 19: ...o out During programming this indicator is active N B Max 3 W If the button panel or the bulbs are used excessively the logic of the control unit may be compromised with possible blocking of all operations TECHNICAL SPECIFICATIONS K2 24V Temperature range 0 55 C Humidity 95 without condensation Power supply voltage 230V 10 120V 60Hz upon request Frequency 50 60 Hz Battery power supply 20 24 5Vdc W...

Page 20: ... WITH BATTERIES If batteries are connected to the control unit when there is a power cut the functioning of the gate is guaranteed up to a charging level of approximately 20V following which a signal is sent by the recharge card to the control unit which blocks the gate and makes the battery signal light flash Once voltage returns we recommend that the gate be fully opened Allow the gate to close ...

Page 21: ...Pag 21 di 28 E N G L I S H MECHANICAL STRIP L 2MT 6 56 FEET code ACG3010 With double safety contact you can cut the length you need ...

Page 22: ...Pag 22 di 28 K2 24V Code BC07059 K2 24V CRX Code BC07058 ELEKTROANSCHLÜSSE D E U T S C H ...

Page 23: ... rot L6 Tor in Öffnungsfase M2 grün L7 Tor in Schließfase M2 rot L8 Befehls Schalttaste K Button grün L9 Programmierung aktiviert rot L10 Programmierung Radio Kode grün RELE RL1 RELE SCHALTET MOTOR 1 AB RL2 RELE SCHALTET MOTOR 1 EIN RL3 RELE SCHALTET MOTOR 2 AB RL4 RELE SCHALTET MOTOR 2 EIN OMNIFET Q1 OMNIFET LEISTUNGSKRAFT STEUERT DEN MOTOR 1 IN ÖFFNUNG UND SCHLIEßUNG Q2 OMNIFET LEISTUNGSKRAFT ST...

Page 24: ... bei geschlossenem Tor auszuführen 1 DIP 1 auf ON und danach DIP 2 auf ON stellen Led L9 das Programmierungsled wird mit einer Frequenz von 1 Sekunde ON und 1 Sekunde OFF 10 Sekunden lang blinken in dieser Zeitspanne können die Kode programmiert werden 2 Die Taste der Fernbedienung innerhalb der vorgegebenen 10 Sekunden normalerweise Kanal A drücken Ist die Fernbedienung korrekt gespeichert sendet...

Page 25: ...ie Funktionierung des Tores wieder herzustellen und zwar indem man irgend eine Schalttaste nach Wahl betätigt KONTROLLAMPE FÜR DIE SIGNALISIERUNG TOR OFFEN COM SIGNAL Diese Kontrolllampe ist dafür zuständig die Position des offenen Tores zu signalisieren dies wenn dieses nur teilweise geöffnet ist oder auch wenn nicht vollständig geschlossen Nur wenn das Tor völlig geschlossen ist erlöscht diese K...

Page 26: ...ontrolle und bewegen sich nicht mehr in der normalen Schließungsposition Die erste Steuerung hat deshalb bei Stromrückkehr komplett zu erfolgen Während dieser Fase sind die Sicherheiten aktiv FERNSENDER MOON FIT SYNCRO WANDFOTOZELLEN FITSYNCRO Code ACG8026 einstellbare Reichweite 10 20mt 49 100 Dank einer Synchronisiereinrichtung sind mehrere sich gegenseitig annähernde Paare möglich Bei mehr als ...

Page 27: ...be made available for inspection purposes to authorised bodies Das voliegende Wartungsbuch enthält die technischen Refernzen und die Eintragungen bezüglich der durchgeführten Eingriffe zur Isntallation Wartung Reparatur und Änderung und muss für eventuelle Inspektionen seistens der zuständigen Stellen zur Verfügung gestellt werden NOME INDIRIZZO TELEFONO NOM ADRESSE TÉlÉPHONE NAME ADDRESS TELEPHON...

Page 28: ...to ad essere incorporato in un impianto costituito da ulteriori elementi Rientra perciò nell Art 4 paragrafo 2 della Direttiva 98 37 CEE Macchine e successive modifiche per cui segnaliamo il divieto di messa in servizio prima che l impianto sia stato dichiarato conforme alle disposizioni della Direttiva Le présent dispositif ne peut fonctionner de manière indépendante étant prévu pour être intégré...

Reviews: