7.2 CIRCULATORS ACTIVATION
Circulator on HP (PUMP 1)
Enabling Pump1 consents compressor start.
The PUMP1 is activated automatically by the
USER INTERFACE
in the
following cases:
1) Request DHW
5HTXHVW.&75LILQVWDOOHGWRURRPWHPSHUDWXUHQRWVDWLV¿HG
In step by ACS in climatization and vice versa is provided a delay time on
the departure of Pump1 (parameter 130) to allow opening / closing of the
3-way valve.
You can also activate the pump 1 via external commands (eg thermo-
stats) in the following two ways:
Pump 1 can also be activated by means of external controls (e.g. room
thermostats), in the following two modes:
By closing the circuit of “Pump 1” contact (clamps L
and K of TERMINAL BLOCK)
2. By bringing “L” 230 V phase to clamp J of TERMINAL
BLOCK. In this way the pump P1 is fed inside the machine
and simultaneously the pump P2 (via the terminal I)
Pump 2 (system):
The PUMP2 should only be used in systems with circuit "HIGH" tempera-
ture (fan coils) and "LOW" temperature (radiant). La pompa P2 è usata nel
circuito di "BASSA" temperatura (radiante).
In the case of call in the area radiating through the J input is commanded
the machine to activate the pump P2 connected to the output I, Electa
simultaneously activates the pump P1.
For the use of systems with circuit "HIGH" temperature (fan coils) and
"LOW" temperature (radiant), contact an authorized service center.
There are three ways of changing the HP operation MODE: depending
on setting of parameter
101
, inside the HP label menu:
-
101=0:
Change through
USER INTERFACE
(and KCTR if installed)
-
101=1:
Change through external contact “Remote Cool/Heat”, heating
mode = open contact
- 101=1
: Change through external contact “Remote Cool/Heat”, heating
mode = closed contact (default value)
MODE change through external contact “Remote Cool/Heat”
(clamps 11- 12 of TERMINAL BLOCK) Par = 1 or 2
Default setting: Par 101=2
1
2
1
7.3 COOLING/HEATING OPERATION MODE
MODE change through
USER INTERFACE
. The operation
mode is inverted by keeping the
Esc
key pressed.
MODE change through KCTR The operation mode is inverted by
keeping the
Esc
key pressed.
2
3
Note:
If Pump1 is activated by the external commands, it will remain active even
if the ELECTA is turned off via the "Remote On/Off" external contact
77
Section I :: User
EN
Summary of Contents for ELECTA Series
Page 40: ...Connessioni sulla TERMINAL BLOCK KEAP 40 Sezione II Installazione e manutenzione IT ...
Page 95: ...Connections on the TERMINAL BLOCK KEAP 95 Section II Installation and maintenance EN ...
Page 151: ...Connexions sur la TERMINAL BLOCK KEAP 151 Section II Installation et entretien FR ...
Page 207: ...Anschlüsse an den TERMINAL BLOCK KEAP 207 Leitungsquersch II Installation und Wartung DE ...
Page 263: ...Conexiones en la TERMINAL BLOCK KEAP 263 Sección II Instalación y mantenimiento ES ...
Page 342: ...342 ...
Page 343: ...343 ...