1.
Remore On/Off: I morsetti 7-8 devono essere cortocircuitati per consentire l’accensione dello
INTERFACCIA UTENTE
e quindi della ELECTA.
2.
In W.S.: The temperature sensor “In W. S.”, for the return water from ELECTA must be disconnected from the PCB.
3.
7HPS:DWHU6XSSO\6\VWHP7KHNȍWHPSHUDWXUHVHQVRUPXVWEHFRQQHFWHGEHWZHHQWHUPLQDOVDW&WRGHWHFWWKHWHPSHUDWXUHRIWKH
water delivered to the radiant system.
4.
Set Point 2: A switch needs to be set up between terminals 13-14 , which enables water production to the second set point when it is closed,
suited for fancoil operation.
5.
Out Signal 0-10Vdc: Mixing valve cables Y and G0 are connected between ter and - (0-10V modulating signal).
6.
Power Supply 24V 6VA: Mixing valve cables G0 and G are connected between terminals 26-27 (24V 6VA power supply).
NOTE: cable G0 of the mixing valve is shared by terminals – and 26, which can accordingly be short circuited.
7.
Out Pump 2: The pump for the radiant system must be connected between terminal I and the neutral of the terminal block.
8.
Either the KCTR can be used as a room thermostat, or a simple thermostat set up between terminals L-K for systems that only have pump P1, or
that have the phase on terminal J for systems where the radiant area is served by pump P2.
1.4 PARAMETER CONFIGURATION
1.
7RDFFHVVWKHFRQ¿JXUDWLRQSDUDPHWHUVLQVHUWSDVVZRUG
2.
3DUDPHWHUFRQ¿JXUDWLRQIURPWKH6HWPHQX
Menù
label
Par
Label
Description
U.m.
Range
Default
Correct
Address
min
max
SEnS
110
P3-4
&RQ¿JXULQJWKHVLJQDOWRWKHWHUPLQDOV
3-4
(Temp. Water Supply
System), on the PCB-TERMINAL BLOCK :
0: STANDARD. Temperature signal from the sensor installed on the
water return. The “In W.S.” connector must be
connected to the PCB-TERMINAL BLOCK. 1: NTC_RADIANT. The
temperature of the water
delivered to the radiant system is measured (sensor duly set up
by the installation technician). The “In W.S.” connector must be
disconnected from the PCB-TERMINAL BLOCK. The temperature is
measured on the storage, for the advanced control of an additional
generator (sensor duly set up by the installation technician). The “In
W.S.” connector must be disconnected from the PCB-TERMINAL
BLOCK.
-
0
3
0
1
16389
Menù
label
Par
Label
Description
U.m.
Range
Default
Correct
Address
min
max
USYS
224
EMA
Maximum hot water temperature to the radiant system
°C
10
60
45
16433
225
ddEU
Disable the use of the dew temperature to calculate the minimum
cold water reading to the radiant system
On:
The set “EN im” value is applied as the minimum temperature of the
cold water to the radiant system(par228)
Off: The value calculated on the “EL im” dew point is applied as
the minimum temperature of the cold water to the radiant system
(par229)
-
On
Off
Off
16434
226
tdEU
Dew Point If the KCTR is not connected, or in case of AMbt, AMbH
or rEMc alarms, this reading is 0
°C
-
-
Read
value
8990
227
StrU
Offset between the dew temperature and the minimum temperature
of the cold water to the radiant system To take into account the type
of radiant system structure, the minimum temperature of the cold
water is provided by the dew temperature plus this value.
°C
-10
10
-2
16435
228
EMin
The value that is used, as the minimum temperature of the cold
water to the radiant system, if the dew temperature “tdEU” is not
available (par226) or if “ddEU” is set as (par225) = On.
°C
12
25
18
16436
229
eLiM
Data from the calculation: “tdEU”(par226) + “StrU”(par227). The va-
lue that is used, as the minimum temperature of the cold water to the
radiant system, if the dew temperature “tdEU” is available (par226)
or if “ddEU” is set as (par225) = Off.
°C
-
-
Read
value
8991
3.
3DUDPHWHUFRQ¿JXUDWLRQIURPWKH³3UJ´PHQX
297
Enclosed documents
EN
Summary of Contents for ELECTA Series
Page 40: ...Connessioni sulla TERMINAL BLOCK KEAP 40 Sezione II Installazione e manutenzione IT ...
Page 95: ...Connections on the TERMINAL BLOCK KEAP 95 Section II Installation and maintenance EN ...
Page 151: ...Connexions sur la TERMINAL BLOCK KEAP 151 Section II Installation et entretien FR ...
Page 207: ...Anschlüsse an den TERMINAL BLOCK KEAP 207 Leitungsquersch II Installation und Wartung DE ...
Page 263: ...Conexiones en la TERMINAL BLOCK KEAP 263 Sección II Instalación y mantenimiento ES ...
Page 342: ...342 ...
Page 343: ...343 ...