“Prg” Menu parameters list 2-2
Men label
Par Label Description
U. m.
Range
Default KCTR
PW
Address
min
max
AFR
241
AFEn
Frost protection mode:
- On: Frost protection by
USER INTERFACE
. The internal protection
must be disabled to PdC (PCB DISPLAY switch 1 OFF)
- Off: Frost protection from PdC controller (PCB DISPLAY switch 1
ON)
-
On
Off
Off
S
16443
242
AFSU
Water temperature (par. 109/111) below which there is the
LQWHUYHQWLRQRIWKH¿UVWOHYHORIIURVWSURWHFWLRQ3XPSDFWLYH
°C
2
-10
2
S
16444
243
AFSA
External air temperature (par. 108) under which you have the
LQWHUYHQWLRQRIWKH¿UVWOHYHORIIURVWSURWHFWLRQ3XPSDFWLYH
°C
2
-10
1
S
16445
244
AF2U
Water temperature (par. 109/111) below which there is the
intervention of the second level of frost protection (water heating by
PdC and / or additional generator)
°C
1
-15
-1
S
16384
245
diFA
Frost protection, differential
Differential applied at temperatures above set (AFSA, AFSU, AF2U),
beyond which disables the respective levels of protection
°C
1
15
5
S
16446
246
AFtU
Water temperature, the output from the heat pump, request the
intervention of the second level of frost protection
°C
5
30
5
S
16447
P1
247
St1
+32Q2IIWLPHUSUR¿OHVWDUW¿UVW2QSHULRG
7LPHZKHQIRUWKH¿UVWWLPHFKDQJHKDSSHQVIURP2IIWR2QLQ
SUR¿OH
h:
min
00:00
En1
08:00
X
16452
248
En1
+32Q2IIWLPHUSUR¿OHHQG¿UVW2QSHULRG
7LPHZKHQIRUWKH¿UVWWLPHFKDQJHKDSSHQVIURP2QWR2IILQ
SUR¿OH
h:
min
St1
St2
12:00
X
16453
249
St2
+32Q2IIWLPHUSUR¿OHVWDUWVHFRQG2QSHULRG
Time when, for the second time, change happens from Off to On, in
SUR¿OH
h:
min
En1
En2
14:00
X
16454
250
En2
+32Q2IIWLPHUSUR¿OHHQGVHFRQG2QSHULRG
Time when, for the second time, change happens from On to Off, in
SUR¿OH
h:
min
St2
23:59
17:00
X
16455
P2
251
St
+32Q2IIWLPHUSUR¿OHVWDUW2QSHULRG
7LPHZKHQFKDQJHKDSSHQVIURP2IIWR2QLQSUR¿OH
h:
min
00:00
En
08:00
X
16456
252
En
+32Q2IIWLPHUSUR¿OHHQG2QSHULRG
7LPHZKHQIRUWKH¿UVWWLPHFKDQJHKDSSHQVIURP2QWR2IILQ
SUR¿OH
h:
min
St
23:59
17:00
X
16457
dAYS
253
MOn
$VVLJQPHQWRIWKHIRXUSUR¿OHV3333WRHDFKZHHNGD\
1=P1 Four time bands, two On and two Off
2=P2 Two time bands, one On and one Off
3=P3 Single time band always On
4=P4 Single time band always Off
-
1
4
1
X
16458
254
tUE
-
1
4
1
X
16459
255
UEd
-
1
4
1
X
16460
256
tHr
-
1
4
1
X
16461
257
Fri
-
1
4
1
X
16462
258
SAt
-
1
4
2
X
16463
259
SUn
-
1
4
4
X
16464
There are also avaiables the following variables
Men label
Par Label Description
U. m.
Range
Default KCTR
PW
Address
min
max
-
-
-
Defrosting active or non-active (read-only)
-
-
-
-
-
-
8967
-
-
-
On / Off unit (read / write)
-
-
-
-
-
-
16385
-
-
-
Mode of operation Summer / Winter (reading and writing)
-
-
-
-
-
-
16387
75
Section I :: User
EN
Summary of Contents for ELECTA Series
Page 40: ...Connessioni sulla TERMINAL BLOCK KEAP 40 Sezione II Installazione e manutenzione IT ...
Page 95: ...Connections on the TERMINAL BLOCK KEAP 95 Section II Installation and maintenance EN ...
Page 151: ...Connexions sur la TERMINAL BLOCK KEAP 151 Section II Installation et entretien FR ...
Page 207: ...Anschlüsse an den TERMINAL BLOCK KEAP 207 Leitungsquersch II Installation und Wartung DE ...
Page 263: ...Conexiones en la TERMINAL BLOCK KEAP 263 Sección II Instalación y mantenimiento ES ...
Page 342: ...342 ...
Page 343: ...343 ...