background image

6

Association, Inc., Batterymarch

Park, Quincy, MA 02269.” These

publications are: 

• AnSI/nFPA no. 70-(Latest Edition)

national Electrical Code. 

• nFPA90A Installation of Air

Conditioning and Ventilating

Systems. 

• nFPA90B Installation of Warm Air

Heating and Air Conditioning

Systems. 

• The equipment has been

evaluated in accordance with the

Code of Federal Regulations,

Chapter XX, Part 3280. 

IMPORTANT INFORMATION
ABOUT EFFICIENCY AND
INDOOR AIR QUALITY

Central cooling and heating

equipment is only as efficient as the

duct system that carries the cooled or

heated air. To maintain efficiency,

comfort and good indoor air quality, it

is important to have the proper

balance between the air being

supplied to each room and the air

returning to the cooling and heating

equipment. 

Proper balance and sealing of the

duct system improves the efficiency

of the heating and air conditioning

system and improves the indoor air

quality of the home by reducing the

amount of airborne pollutants that

enter homes from spaces where the

ductwork and/or equipment is

located. The manufacturer and the

U.S. Environmental Protection

Agency’s EnERGY STAR Program

recommend that central duct systems

be checked by a qualified contractor

for proper balance and sealing. 

DUCT LEAkS CAN CREATE AN

UNBALANCED SYSTEM AND

DRAW POLLUTANTS SUCH AS

DIRT, DUST, FUMES AND ODORS

INTO THE HOME CAUSING

PROPERTY DAMAGE. FUMES

AND ODORS FROM TOXIC,

VOLATILE OR FLAMMABLE

CHEMICALS, AS WELL AS

AUTOMOBILE EXHAUST AND

CARBON MONOXIDE (CO), CAN

BE DRAWN INTO THE LIVING

SPACE THROUGH LEAkING

DUCTS AND UNBALANCED DUCT

SYSTEMS CAUSING PERSONAL

INJURY OR DEATH (SEE FIGURE

2). 

• IF AIR-MOVING EqUIPMENT OR

DUCTWORk IS LOCATED IN

GARAGES OR OFF-GARAGE

STORAGE AREAS - ALL JOINTS,

SEAMS, AND OPENINGS IN THE

EqUIPMENT AND DUCT MUST

BE SEALED TO LIMIT THE

MIGRATION OF TOXIC FUMES

AND ODORS INCLUDING

CARBON MONOXIDE FROM

MIGRATING INTO THE LIVING

SPACE. 

• IF AIR-MOVING EqUIPMENT OR

DUCTWORk IS LOCATED IN

SPACES CONTAINING FUEL

BURNING APPLIANCES SUCH

AS WATER HEATERS OR

BOILERS - ALL JOINTS, SEAMS,

AND OPENINGS IN THE

EqUIPMENT AND DUCT MUST

ALSO BE SEALED TO PREVENT

DEPRESSURIZATION OF THE

SPACE AND POSSIBLE

MIGRATION OF COMBUSTION

BYPRODUCTS INCLUDING

CARBON MONOXIDE INTO THE

LIVING SPACE. 

IMPROPER INSTALLATION, OR

INSTALLATION NOT MADE IN

ACCORDANCE WITH THE UL

CERTIFICATION OR THESE

INSTRUCTIONS, CAN RESULT IN

UNSATISFACTORY OPERATION

AND/OR DANGEROUS CONDI-

TIONS AND ARE NOT COVERED BY

THE UNIT WARRANTY. 

IN COMPLIANCE WITH

RECOGNIZED CODES, IT IS

RECOMMENDED THAT AN

AUXILIARY DRAIN PAN BE

INSTALLED UNDER ALL

EVAPORATOR COILS OR UNITS

CONTAINING EVAPORATOR COILS

OR AIR HANDLERS USED WITH

EVAPORATOR COILS THAT ARE

LOCATED IN ANY AREA OF A

STRUCTURE DAMAGE TO THE

BUILDING OR BUILDING CONTENTS

MAY OCCUR AS A RESULT OF AN

OVERFLOW OF THE COIL DRAIN

PAN OR A STOPPAGE IN THE

PRIMARY CONDENSATE DRAIN

PIPING.

required for the job specification. 

• Read the entire instructions before

starting the installation. 

• Some building codes require extra

cabinet insulation and gasketing

when unit is installed in attic

applications. 

• If installed in an unconditioned

space, apply caulking around the

power wires, control wires,

refrigerant tubing and condensate

line where they enter the cabinet.

Seal the power wires on the inside

where they exit conduit opening.

Caulking is required to prevent air

leakage into and condensate from

forming inside the unit, control box,

and on electrical controls. 

• Install the unit in such a way as to

allow necessary access to the

coil/pump and blower/control

compartment. 

• Install the unit in a level position to

ensure proper condensate

drainage. Make sure unit is level in

both directions within 1/8”. 

• Install the unit in accordance with

any local code which may apply

and the national codes. Latest

editions are available from:

“national Fire Protection

RECEIVING

Immediately upon receipt, all cartons

and contents should be inspected for

transit damage. Units with damaged

cartons should be opened

immediately. If damage is found, it

should be noted on the delivery

papers, and a damage claim filed

with the last carrier. 

• After unit has been delivered to job

site, remove carton, taking care

not to damage unit. 

• Check the unit rating plate for unit

size, voltage, phase, etc. to be

sure equipment matches what is

NOTICE

NOTICE

!

WARNING

FIGURE 3

MIGRATION OF DANGEROUS SUBSTANCES, FUMES, AND ODORS INTO LIVING SPACES

Summary of Contents for RW1P

Page 1: ...92 24161 150 04 SUPERSEDES 92 24161 150 03 INSTALLATION INSTRUCTIONS HYDRONIC AIR HANDLER RW1T RW1P RWMV ISO 9001 2008...

Page 2: ...N MAY RESULT IN PERSONAL INJURY SHEET METAL PARTS MAY HAVE SHARP EDGES OR BURRS USE CARE AND WEAR APPROPRIATE PROTECTIVE CLOTHING CAUTION NOTICE SAFETY INFORMATION WHEN AN AIR HANDLER IS INSTALLED SO...

Page 3: ...nown to the State of California to cause cancer or birth defects such as fiberglass insulation lead in brass and combustion products from natural gas All new equipment shipped for sale in California w...

Page 4: ...ERTIFIED BY UL 1 DOOR SWITCH 2 JUNCTION BOX 3 TRANSFORMERS 4 CAPACITORS 5 LOW VOLTAGE THERMOSTAT TERMINAL 6 BLOWER 7 PUMP IF REQUIRED 8 WATER INLET OUTLET FOR 14 HAH 9 WATER OUTLET INLET FOR 14 HAH 10...

Page 5: ...UL 1 DOOR SWITCH 2 JUNCTION BOX 3 TRANSFORMERS 4 TERMINAL BLOCK 5 CONTROLBOARD 6 BLOWER 7 PUMP IF REQUIRED 8 WATER INLET OUTLET FOR 14 HAH 9 WATER OUTLET INLET FOR 14 HAH 10 BLOWER MOTOR 11 HYDRONIC C...

Page 6: ...SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CARBON MONOXIDE INTO THE LIVING SPACE IMPROPER INSTALLATION OR INSTALLATION NOT MADE IN ACCORD...

Page 7: ...TY The design of air handlers with input ratings as listed in the tables under Figure 4 are certified by UL for the clearances to combustible materials shown in inches See name rating plate and cleara...

Page 8: ...SIDE OPTIONAL RETURN AIR CUTOUT EITHER SIDE A I R F L O W A B C REF D E F G H ST A1242 03 X0 Model A B C D E F RW 04A2414 14 13 13 16 13 16 19 3 3 8 RW 06A3617 17 1 2 16 1 2 16 1 2 16 13 16 19 4 5 8...

Page 9: ...llation Instructions and the Filter Pressure Drop Determine both static pressures at 1600 CFM Wet Coil Pressure Drop 0 3 in W C From Coil Manufacturer s Installation Instructions External Static Press...

Page 10: ...x 8 254 x 203 10 x 10 254 x 254 11 x 11 279 x 279 Blower Motor Type EcoTech ECM Type Pump Type Wet Rotor Pump Power Supply V HZ PH 115 60 1 Pump Motor RLA LRA Amps 1 8 Pump HP W 1 8 86 Pump Maximum Wo...

Page 11: ...ave a greater than normal resistance to air flow This can adversely affect air handler operation BE SURE TO CHECk AIR FLOW IMPORTANT When using outside air design and adjust the system to maintain a r...

Page 12: ...s or runs with many turns and elbows 2 If summer air conditioning or heat pump is desired position the indoor coil on the supply air end of the unit Insure that no air can bypass this coil 3 Connect t...

Page 13: ...nt Methods Using Straps Method 1 Use 4 8 x 3 4 sheet metal screws for each strap The straps should be vertical against the air handler sides and not pull away from the air handler sides Method 2 Fold...

Page 14: ...present the piping should be supported immediately adjacent to the component On vertical runs copper tubing should be supported at each floor level or at a maximum of every 10 feet Thermal Expansion o...

Page 15: ...an open loop system when configured to simultaneously deliver both domestic hot water and space heating By definition if the circuit is sealed off from the atmosphere at all locations as is true for m...

Page 16: ...DV3 to which a hose MUST be connected and draining to a sink drain or outdoors STEP 4 CLOSE drain valves 1 2 DV1 and DV2 and OPEn ball valve 2 BV2 STEP 5 OPEn cold water supply main valve ball valve...

Page 17: ...talled so that the electrical components are protected from water condensate Before proceeding with the electrical connections be certain that the voltage frequency and phase corresponds to that speci...

Page 18: ...olt Wiring Factory 115 Volt Wiring Junction Box L1 L2 FIGURE 13 THERMOSTAT WIRING DIAGRAMS MODULATING AIR HANDLER W SINGLE STAGE A C FIRST STAGE HEAT COOL AUX HEATING FAN 24VAC HOT 24 VAC COMMON SINGL...

Page 19: ...115 Volt Wiring Junction Box L1 L2 FIGURE 13A THERMOSTAT WIRING DIAGRAMS MODULATING AIR HANDLER W SINGLE STAGE A C FIRST STAGE HEAT COOL AUX HEATING FAN 24VAC HOT 24 VAC COMMON 24 VOLT SINGLE STAGE A...

Page 20: ...ON MODULATING NOTES 1 For proper operation of an open loop system refer to Figures 11 and 17 the jumper shunt position on PCB point P7 should be in the FS position 2 When changing shunt position ensur...

Page 21: ...BOARD MODULATING NOTES 1 For proper operation of an open loop system refer to Figures 11 and 17 the jumper shunt position on PCB point P7 should be in the FS position 2 When changing shunt position e...

Page 22: ...Turn thermostat On and switch system to the heating mode The thermostat shall be set higher than the actual room temperature this will cause the circulator to energize and initiate the heating cycle I...

Page 23: ...off the pump and go into a 5 minute delay If the supply temperature is adequate the main blower will then be energized and run for 30 seconds After the 30 second delay the control will monitor the sup...

Page 24: ...6 15 0 7 17 0 8 17 0 9 22 CFM L s Air Delivery External Static Pressure Inches Water Column kPa Low 642 339 612 322 591 311 524 273 Med low 711 377 684 362 655 346 624 329 578 303 526 274 Med high 890...

Page 25: ...ISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPTING ANY MAINTE NANCE FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCk RESULTING IN PERSONAL INJURY OR DEATH WARNING DO NOT OPERATE THE SYSTEM FOR E...

Page 26: ...induced draft blower motor must be cleaned periodically by a qualified installer service agency or the gas supplier to prevent the possibility of overheating due to an accumulation of dust and dirt on...

Page 27: ...a d e z i s y l r e p o r p m I g n i t t e s p a t d e e p s r o t o m k c e h C w o l f r i a r o o d n i r e p o r p m I Call for domes c hot water air handler disabled un l call ends Unit is opera...

Page 28: ...MANENTLY GROUNDED AND CONFORM TO I E C N E C C E C NATIONAL WIRING REGULATIONS AND LOCAL CODES AS APPLICABLE REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL 105C MIN FIELD IN...

Page 29: ...29 FIGURE 21 ELECTRICAL WIRING DIAGRAM PSC MOTORS RW1P...

Page 30: ...RM TO I E C N E C C E C NATIONAL WIRI N G REGULATIONS AND LOC AL C ODES A S APPLICABLE R EPLACEMENT WIR E MUST BE THE SAME SIZE AND TYPE OF I NS ULATION AS ORIGINAL 105C MIN FIELD INS TALLED FACTOR Y...

Page 31: ...C ONFORM TO I E C N E C C E C NATIONAL WIRI N G REGULATIONS AND LOC AL C ODES A S APPLICABLE R EPLACEMENT WIR E MUST BE THE SAME SIZE AND TYPE OF I NS ULATION AS ORIGINAL 105C MIN FIELD INS TALLED FAC...

Page 32: ...32 FIGURE 24 ELECTRICAL WIRING DIAGRAM...

Page 33: ...33...

Page 34: ...34...

Page 35: ...35...

Page 36: ...36 CM 0617...

Reviews: