Rheem RW1P Installation Instructions Manual Download Page 14

14

PLUMBING 

Codes: 

The RW1T air handler is used in potable

water systems. Therefore, it is important

to observe all local sanitary codes when

installing water lines. The water supply

mating connection to the Hydronic Air

Handler is made via the two 3/4 in. dia.

copper stubs labeled “WATER In” and

“WATER OUT” (see Figure 1). 
All associated hydronic piping MUST

comply with ICC, UPC and any other

local codes or ordinances having

jurisdiction.  USE POTABLE GRADE

COPPER PIPInG AnD BRASS

APPURTEnAnCES OnLY.  

Soldering Copper Tubing: 

The common method of joining copper

tubing in hydronic heating systems is

soft soldering.  Plumbing codes do not

allow solders containing lead to be used

for domestic water service. USE OnLY

95/5 tin/antimony solder for all piping

systems that incorporate a domestic

water supply. 

NOTE:

Precautions must be taken

during soldering to avoid debris or

solder from lodging in piping system.

Water Storage Tank: 

When connecting directly to a water

storage tank it is necessary to ensure

the water flow rate does not become

excessive. Excessive water flow can

result in increased system noise and

potential system damage. In order to

regulate the flow it is required that an

adjustable valve be placed between the

air handler outlet and the storage tank

Rheem Accessory HC. Furthermore, two

pressure taps will need to be installed,

the first located between the air handler

outlet and the adjustable valve as near

as possible to the outlet, and the second

on the inlet water attached as near as

possible to the inlet. While the water

pump is engaged the adjustable valve

will be closed until the pressure

difference between the outlet and the

inlet is greater than 13.5 PSID. 

Tubing Insulation:

Any tube-conveying fluid at a

temperature greater than that of the

surrounding air releases heat. 
Insulate all accessible hot water lines

and associated valves with material,

such as expanded neoprene or

polyurethane 3/8-in. to 1⁄2-in. thick. 
Match the pipe sleeve’s inside diameter

to the pipe’s outside diameter for a snug

fit. Place the pipe sleeve so the seam

will be face down on the pipe.  Tape,

wire, or clamp insulation every foot or

two to secure it to the pipe. If taping is

desired, use acrylic tape instead of duct

tape.

Copper Tubing Support: 

Copper tubing must be properly

supported to prevent sagging or

buckling.  On horizontal runs with hard

temper tubing, the following maximum

support spacing is suggested: 

• 1/2 in. to 3/4 in. tube: 5 feet maximum

spacing 

•  1 in. to 1-1/4 in. tube: 6 feet maximum

spacing

The above suggested spacing does not

account for extra weight of piping

components such as an expansion tank,

etc. When such components are

present, the piping should be supported

immediately adjacent to the component.    
On vertical runs, copper tubing should

be supported at each floor level or at a

maximum of every 10 feet.

Thermal Expansion of Piping: 

In all hydronic systems, piping

undergoes temperature swings as the

system operates. This causes changes

in the length of the piping due to thermal

expansion. 
If the piping is rigidly mounted, this

expansion can cause annoying popping

or squeaking sounds and, in extreme

cases, the piping can even buckle.  
To counter expansion movement,

design piping circuits with sufficient

elbows, tees or expansion loops (only

used in large systems) or piping

supports that allow the tubing to expand

and contract freely.  
Another alternative is to install an

expansion compensator fitting capable

of absorbing the movement.

Hydronic Resistance of

Fittings, Valves, and Other

Devices: 

Before the total hydronic resistance

of a piping circuit can be found, the

individual hydronic resistances of all

fittings, valves, or other such

components must be determined.

One approach is to consider each

fitting, valve, or other device as an

equivalent length of copper tube of

the same pipe size (see Table 1).  
By using the equivalent length of

piping for all components in the

circuit, the circuit can be treated as if

it were a single piece of pipe having

a length equal to the sum of the

actual pipe length, the total

equivalent lengths of all fittings,

valves, or other devices. Refer to

Figure 9 and the calculation of

equivalent lengths.

Pipe Sizing Considerations: 

When selecting a pipe size for a

given flow rate, the resulting average

flow velocity should be between 2

and 4 feet per second. 
At water flow velocities of

approximately 2 feet per second,

flowing water will carry air bubbles

along a vertical pipe.  Average flow

velocities of 2 feet per second or

higher can draw along air bubbles in

a downward flow.  At the above

stated velocities air bubbles shall be

routed to an air separator where they

can be collected and discharged from

the system. Use Taco 4900 series air

separator, Model 49-075, or

equivalent (field supplied). 
Average flow velocities higher than 4

feet per second could cause flow

noise and should be avoided.

Expansion Tank: 

All liquids used in hydronic heating

systems expand when heated.  For

all practical purposes, liquids are

incompressible.  Any container

completely filled with a liquid and

sealed from the atmosphere will

experience a rapid increase in

pressure as the liquid is heated. 
To prevent this from occurring, all

closed-loop hydronic systems MUST

be equipped with an expansion tank.

Refer to expansion tank man u fac -

turer’s instructions for proper sizing

and installation. 

Water circulation:

The hydronic air handler has a strict

in press cycle which will circulate the

water in the coil for 6 minutes per day

to prevent water stagnation.

Summary of Contents for RW1P

Page 1: ...92 24161 150 04 SUPERSEDES 92 24161 150 03 INSTALLATION INSTRUCTIONS HYDRONIC AIR HANDLER RW1T RW1P RWMV ISO 9001 2008...

Page 2: ...N MAY RESULT IN PERSONAL INJURY SHEET METAL PARTS MAY HAVE SHARP EDGES OR BURRS USE CARE AND WEAR APPROPRIATE PROTECTIVE CLOTHING CAUTION NOTICE SAFETY INFORMATION WHEN AN AIR HANDLER IS INSTALLED SO...

Page 3: ...nown to the State of California to cause cancer or birth defects such as fiberglass insulation lead in brass and combustion products from natural gas All new equipment shipped for sale in California w...

Page 4: ...ERTIFIED BY UL 1 DOOR SWITCH 2 JUNCTION BOX 3 TRANSFORMERS 4 CAPACITORS 5 LOW VOLTAGE THERMOSTAT TERMINAL 6 BLOWER 7 PUMP IF REQUIRED 8 WATER INLET OUTLET FOR 14 HAH 9 WATER OUTLET INLET FOR 14 HAH 10...

Page 5: ...UL 1 DOOR SWITCH 2 JUNCTION BOX 3 TRANSFORMERS 4 TERMINAL BLOCK 5 CONTROLBOARD 6 BLOWER 7 PUMP IF REQUIRED 8 WATER INLET OUTLET FOR 14 HAH 9 WATER OUTLET INLET FOR 14 HAH 10 BLOWER MOTOR 11 HYDRONIC C...

Page 6: ...SEALED TO PREVENT DEPRESSURIZATION OF THE SPACE AND POSSIBLE MIGRATION OF COMBUSTION BYPRODUCTS INCLUDING CARBON MONOXIDE INTO THE LIVING SPACE IMPROPER INSTALLATION OR INSTALLATION NOT MADE IN ACCORD...

Page 7: ...TY The design of air handlers with input ratings as listed in the tables under Figure 4 are certified by UL for the clearances to combustible materials shown in inches See name rating plate and cleara...

Page 8: ...SIDE OPTIONAL RETURN AIR CUTOUT EITHER SIDE A I R F L O W A B C REF D E F G H ST A1242 03 X0 Model A B C D E F RW 04A2414 14 13 13 16 13 16 19 3 3 8 RW 06A3617 17 1 2 16 1 2 16 1 2 16 13 16 19 4 5 8...

Page 9: ...llation Instructions and the Filter Pressure Drop Determine both static pressures at 1600 CFM Wet Coil Pressure Drop 0 3 in W C From Coil Manufacturer s Installation Instructions External Static Press...

Page 10: ...x 8 254 x 203 10 x 10 254 x 254 11 x 11 279 x 279 Blower Motor Type EcoTech ECM Type Pump Type Wet Rotor Pump Power Supply V HZ PH 115 60 1 Pump Motor RLA LRA Amps 1 8 Pump HP W 1 8 86 Pump Maximum Wo...

Page 11: ...ave a greater than normal resistance to air flow This can adversely affect air handler operation BE SURE TO CHECk AIR FLOW IMPORTANT When using outside air design and adjust the system to maintain a r...

Page 12: ...s or runs with many turns and elbows 2 If summer air conditioning or heat pump is desired position the indoor coil on the supply air end of the unit Insure that no air can bypass this coil 3 Connect t...

Page 13: ...nt Methods Using Straps Method 1 Use 4 8 x 3 4 sheet metal screws for each strap The straps should be vertical against the air handler sides and not pull away from the air handler sides Method 2 Fold...

Page 14: ...present the piping should be supported immediately adjacent to the component On vertical runs copper tubing should be supported at each floor level or at a maximum of every 10 feet Thermal Expansion o...

Page 15: ...an open loop system when configured to simultaneously deliver both domestic hot water and space heating By definition if the circuit is sealed off from the atmosphere at all locations as is true for m...

Page 16: ...DV3 to which a hose MUST be connected and draining to a sink drain or outdoors STEP 4 CLOSE drain valves 1 2 DV1 and DV2 and OPEn ball valve 2 BV2 STEP 5 OPEn cold water supply main valve ball valve...

Page 17: ...talled so that the electrical components are protected from water condensate Before proceeding with the electrical connections be certain that the voltage frequency and phase corresponds to that speci...

Page 18: ...olt Wiring Factory 115 Volt Wiring Junction Box L1 L2 FIGURE 13 THERMOSTAT WIRING DIAGRAMS MODULATING AIR HANDLER W SINGLE STAGE A C FIRST STAGE HEAT COOL AUX HEATING FAN 24VAC HOT 24 VAC COMMON SINGL...

Page 19: ...115 Volt Wiring Junction Box L1 L2 FIGURE 13A THERMOSTAT WIRING DIAGRAMS MODULATING AIR HANDLER W SINGLE STAGE A C FIRST STAGE HEAT COOL AUX HEATING FAN 24VAC HOT 24 VAC COMMON 24 VOLT SINGLE STAGE A...

Page 20: ...ON MODULATING NOTES 1 For proper operation of an open loop system refer to Figures 11 and 17 the jumper shunt position on PCB point P7 should be in the FS position 2 When changing shunt position ensur...

Page 21: ...BOARD MODULATING NOTES 1 For proper operation of an open loop system refer to Figures 11 and 17 the jumper shunt position on PCB point P7 should be in the FS position 2 When changing shunt position e...

Page 22: ...Turn thermostat On and switch system to the heating mode The thermostat shall be set higher than the actual room temperature this will cause the circulator to energize and initiate the heating cycle I...

Page 23: ...off the pump and go into a 5 minute delay If the supply temperature is adequate the main blower will then be energized and run for 30 seconds After the 30 second delay the control will monitor the sup...

Page 24: ...6 15 0 7 17 0 8 17 0 9 22 CFM L s Air Delivery External Static Pressure Inches Water Column kPa Low 642 339 612 322 591 311 524 273 Med low 711 377 684 362 655 346 624 329 578 303 526 274 Med high 890...

Page 25: ...ISCONNECT MAIN ELECTRICAL POWER TO THE UNIT BEFORE ATTEMPTING ANY MAINTE NANCE FAILURE TO DO SO CAN CAUSE ELECTRICAL SHOCk RESULTING IN PERSONAL INJURY OR DEATH WARNING DO NOT OPERATE THE SYSTEM FOR E...

Page 26: ...induced draft blower motor must be cleaned periodically by a qualified installer service agency or the gas supplier to prevent the possibility of overheating due to an accumulation of dust and dirt on...

Page 27: ...a d e z i s y l r e p o r p m I g n i t t e s p a t d e e p s r o t o m k c e h C w o l f r i a r o o d n i r e p o r p m I Call for domes c hot water air handler disabled un l call ends Unit is opera...

Page 28: ...MANENTLY GROUNDED AND CONFORM TO I E C N E C C E C NATIONAL WIRING REGULATIONS AND LOCAL CODES AS APPLICABLE REPLACEMENT WIRE MUST BE THE SAME SIZE AND TYPE OF INSULATION AS ORIGINAL 105C MIN FIELD IN...

Page 29: ...29 FIGURE 21 ELECTRICAL WIRING DIAGRAM PSC MOTORS RW1P...

Page 30: ...RM TO I E C N E C C E C NATIONAL WIRI N G REGULATIONS AND LOC AL C ODES A S APPLICABLE R EPLACEMENT WIR E MUST BE THE SAME SIZE AND TYPE OF I NS ULATION AS ORIGINAL 105C MIN FIELD INS TALLED FACTOR Y...

Page 31: ...C ONFORM TO I E C N E C C E C NATIONAL WIRI N G REGULATIONS AND LOC AL C ODES A S APPLICABLE R EPLACEMENT WIR E MUST BE THE SAME SIZE AND TYPE OF I NS ULATION AS ORIGINAL 105C MIN FIELD INS TALLED FAC...

Page 32: ...32 FIGURE 24 ELECTRICAL WIRING DIAGRAM...

Page 33: ...33...

Page 34: ...34...

Page 35: ...35...

Page 36: ...36 CM 0617...

Reviews: