AIR CONDITIONER Wall Mounted Type

OPERATING MANUAL

Remote Controller Overview and Operations

Note for timer settings:

Any interruption of the power supply, such as a blackout or cutting off of a circuit breaker, makes the set internal clock go wrong.
In such a case, the TIMER indicator on the indoor unit blinks, and you need to readjust the setting.

 ON timer or OFF timer

1.

  Turn on the indoor unit by pressing the Start/Stop button.

OPERATION indicator on the indoor unit turns on.
If the indoor unit is already operating, skip this step.

2.

  Press the ON timer button or the OFF timer button.

Clock indicator on the remote controller display starts blinking, and 
TIMER indicator on the indoor unit turns on.

3.

  Adjust the time by pressing the SELECT button within about 5 

seconds, while the clock indicator is blinking.
(About 5 seconds later, the remote controller display returns to 
standby screen.)

To cancel the timer and return to the normal operation, press the 
CANCEL button.
To redo the timer setting, perform step 2 and 3.

Program timer (combined use of the ON timer and the OFF timer)

You can set an integrated ON–OFF or OFF–ON timer.
Either of the timer whose con

fi

 gured starting time is closer to the 

current time works 

fi

 rst, and the order of timer operation is displayed 

as follows:

Timer

Indicator on remote controller display

ON–OFF timer

OFF–ON timer

The timer that is set later starts counting down after the counting 
down of the preceding timer is 

fi

 nished.

Notes:

• If you change the setting value for the timer after the program timer 

is set, the counting down of the timer will be reset at that moment.

• Time setting for each combination should be within a span of 24 hours.

SLEEP timer

1.

  Press the SLEEP timer button to activate the SLEEP timer.

OPERATION indicator and TIMER indicator on the indoor unit turns 
on.

2.

  Adjust the time by pressing the SELECT button within about 5 

seconds, while the clock indicator is blinking.
(About 5 seconds later, the remote controller display returns to 
standby screen.)
Each time you press the button, the time changes as follows:

9.0

7.0

5.0

3.0

2.0

1.0

0.5

hours

(30 min.)

To repeat the timer, press the SLEEP timer button when 

 

indicator is not displayed on the remote controller display.

To help you to fall asleep comfortably and prevent excessive warming 
or cooling in sleep, the SLEEP timer controls the temperature setting 
automatically in accordance with the set time shown as follows. The 
air conditioner completely turns off after the set time has elapsed.

In HEAT mode

Set 
temperature

Set time

1 hour

Set time

1 hour

1.5 hour

30 min.

2 °F (1 °C)  4 °F 

(2 °C)

6 °F 

(3 °C)

8 °F 

(4 °C)

4 °F 

(2 °C)

2 °F (1 °C)

In COOL or DRY mode

Timer Operation

 Remote controller custom code setting

Use the following steps to select the custom 
code of the remote controller.
(Note that the air conditioner cannot receive 
a signal if the air conditioner has not been set 
for the matching custom code.)
1.  Press the START/STOP button until 

only the clock is displayed on the remote 
controller display.

2.  Press the MODE button for at least 

fi

 ve 

seconds to display the current custom code 
(initially set to A).

3.  Press the TEMP. (  /  ) button to change the custom code between 

A

B

C

D.

Match the code on the display to the air conditioner custom code.

4.  Press the MODE button again to return to the clock display. The 

custom code will be changed.

If no buttons are pressed within 30 seconds after the custom code 
is displayed, the system returns to the original display. In this case, 
start again from step 1.

The air conditioner custom code is set to A prior to shipment.
Contact our authorized service personnel to change the custom code.

Depending on the remote controller, the custom code may return to 
custom code A when the batteries are replaced. In this case, if you 
use a code other than A, reset the code after replacing the batter-
ies. If you do not know the air conditioner custom code setting, try 
each of the custom codes A

B

C

D. until you 

fi

 nd the code which 

operates the air conditioner.

 Wired Remote Controller (Option)

The optional wired remote controller can be used. When you use the re-
mote controller, there are the following differences as compared with using 
the wireless remote controller.
[Examples of additional functions for wired remote controller]
  • Weekly timer
  • Temperature set back timer
  * Depending on the remote controller type.
You can use both wired and wireless remote controller simultaneously, 
however, the following functions will be restricted.
  • SLEEP timer
  • ON/OFF timer
  • MIN. HEAT operation
  • POWERFUL operation

 Filter indicator (Installer setting)

• This function can be used if activated during installation.

Please consult authorized service personnel when using this function.

• The economy indicator will blink when it is time to clean the air 

fi

 lters.

Clean the 

fi

 lter referring to “Cleaning the air 

fi

 lters”.

After cleaning, press the “MANUAL AUTO” button on the indoor unit for 
less than 3 seconds.

9333003269_OM.indb   5

9333003269_OM.indb   5

2016/11/28   下午 05:46:25

2016/11/28   下午 05:46:25

Summary of Contents for RIWH07AVFJ

Page 1: ...re that they do not play with the appliance Do not start or stop the operation of this product by inserting or pulling out the power plug or by turning on or off the circuit breaker Do not use flammab...

Page 2: ...direction louver Power diffuser 3 7 6 5 4 2 1 3 2 1 4 In SWING operation power diffuser does not move 6 Drain hose 7 Remote controller signal receiver CAUTION For appropriate signal transmission betwe...

Page 3: ...ng 8 Press the C F button to select the preferred temperature unit Factory setting is F Notes Use specified type of batteries only Do not mix different types or new and used batteries together Batteri...

Page 4: ...rection louver Each time you press the button the vertical airflow direction louver swings as follows COOL DRY or FAN mode HEAT or FAN mode 1 2 3 7 6 5 4 1 2 3 4 5 6 7 Notes SWING operation may stop t...

Page 5: ...nce with the set time shown as follows The air conditioner completely turns off after the set time has elapsed In HEAT mode Set temperature Set time 1 hour Set time 1 hour 1 5 hour 30 min 2 F 1 C 4 F...

Page 6: ...ruption such as a blackout the air conditioner stops once But it restarts automatically and performs previous operation when the power supply is resumed If any power interruption occurs after the time...

Page 7: ...internal parts throughly before you perform normal operation Additional inspection After long period of use accumulated dust inside the indoor unit may reduce the product performance even if you have...

Page 8: ...the Automatic Defrosting operation while the OPERATION indicator is flashing 6 In DRY mode the indoor unit operates at low fan speed to adjust the room humidity and may stop from time to time When the...

Page 9: ...rant ou en d connectant la prise d alimentation ou bien en activant ou en d sactivant le disjoncteur N utilisez pas de gaz inflammables proximit de cette unit Ne vous exposez pas directement au flux...

Page 10: ...vertical Diffuseur de puis sance 3 7 6 5 4 2 1 3 2 1 4 En fonctionnement SWING OSCILLATION le diffuseur de puissance ne se d place pas 6 Tuyau de vidange 7 R cepteur du signal de t l commande ATTENTI...

Page 11: ...nfiguration d usine et le F Remarques Utilisez uniquement le type de piles sp cifi es Ne pas m langer diff rents types de piles ni de piles nouvelles et usag es ensemble Avec une utilisation normale l...

Page 12: ...volet de direction du flux d air vertical oscille comme suit Mode COOL REFROIDISSE MENT DRY D SHUMIDIFICA TION ou FAN VENTILATEUR Mode HEAT CHAUF FAGE ou FAN VENTILA TEUR 1 2 3 7 6 5 4 1 2 3 4 5 6 7...

Page 13: ...ne configur e En pareil cas l indicateur TIMER MINUTERIE de l unit int rieure clignote et vous devez rajuster le r glage Minuterie ON MARCHE ou minuterie OFF ARR T 1 Allumez l unit int rieure en appuy...

Page 14: ...il y a eu une d faillance de la minuterie Dans un tel cas r initialisez la minuterie pour le temps opportun Fonctionnements d fectueux caus s par d autres dispositifs lectriques L utilisation d autres...

Page 15: ...TILATEUR pendant une demi journ e afin de s cher compl tement les pi ces internes Inspections compl mentaires Apr s une longue p riode d utilisation la poussi re accumul e l int rieur de l unit int ri...

Page 16: ...UMIDIFICATION l unit int rieure fonctionne basse vitesse du ventilateur afin de r gler l humidit de la pi ce et peut s arr ter de temps en temps Lorsque la vitesse du ventilateur est r gl e sur QUIET...

Page 17: ...que no jueguen con el aparato No iniciar o detener el funcionamiento de este producto insertando o sacando el enchufe de la alimentaci n o de encender o apagar el interruptor de circuito No utilice g...

Page 18: ...n del aire vertical Difusor de po tencia 3 7 6 5 4 2 1 3 2 1 4 En la operaci n SWING VAIV N el difusor de potencia no se mueve 6 Manguera de drenado 7 Receptor de se al del control remoto ATENCI N Par...

Page 19: ...es de bater as tampoco combine nuevas con usadas Las bater as pueden usarse durante cerca de 1 a o en uso ordinario Si el rango del control remoto se acorta de manera evidente reemplace las bater as y...

Page 20: ...de direcci n del aire vertical oscila de la siguiente manera ModoCOOL ENFRIAMIENTO DRY DES HUMECTACI N oFAN VENTILADOR Modo HEAT CALEFACCI N O FAN VENTILADOR 1 2 3 7 6 5 4 1 2 3 4 5 6 7 Notas La opera...

Page 21: ...APAGADO AUTOM TICO controla el ajuste de temperatura autom ticamente de acuerdo con el tiempo establecido como se muestra a continuaci n El acondicionador de aire se apaga por completo una vez que tr...

Page 22: ...re acondicionado se detiene de inmediato Pero se reinicia autom ticamente y realiza la operaci n previa cuando se reanude la alimentaci n el ctrica Si la interrupci n de energ a se produce despu s del...

Page 23: ...artes internas completamente antes de llevar a cabo la operaci n normal Inspecci n adicional Despu s de un per odo prolongado de uso la acumulaci n de polvo dentro de la unidad de interior puede reduc...

Page 24: ...or OPERATION FUNCIONAMIENTO parpadea 6 En el modo DRY deshumectaci n la unidad de interior funciona a baja velocidad del ventilador para ajustar la humedad ambiente tal vez se detenga de vez en cuando...

Reviews: