DSPbR EDGE
Series User’s Manual
Asia Pacific | EMEA | Americas
58
BUTTONS:
To reset the DSPbR EDGE back to the Factory Default settings will mean a complete reset of all RF configuration settings and
alarm threshold parameters as well as the IP address parameters. To do this, simply press an
d hold buttons “A” and “B” for
more than 10 seconds while the READY LED is on.
NOTE:
This will cause the IP address, subnet and gateway addresses and all other configuration data
to be reset back to factory default address.
Factory Default settings
DHCP
- Disabled
IP Address
- 192.168.1.200
Subnet Mask
- 255.255.255.0
Gateway
- 192.168.1.254
Level 1 Username:
user
Level 1 Password:
user
Level 2 Username:
admin
Level 2 Password
: admin
Level 3 Username:
master
Level 3 Password
: master
LABELS:
External Interface Connectors:
Shows the layout of the External Interface Connectors located on the backplane adjacent to the System Controller (SC) module.
EXTERNAL ALARM INPUTS:
The DSPbR EDGE has four (4) external alarm monitoring inputs. These inputs are rated as follows;
Three (3) inputs are configurable for analogue or digital operation.
Analog Voltage Sense:
-60 to +60 V sense.
Digital Voltage Sense:
Logic “0” < 2.5VDC.
Logic “1” > 2.5VDC.
One (1) input is compatible with the RFI SAM0000-TS Temperature Sensor.
All four (4) inputs are protected for -75 to +75 V
ALARM RELAY OUTPUTS:
The DSPbR EDGE has two (2) alarm relays (Minor and Major alarms
’ outputs).
The contacts on these relays are rated as follows;
N.O. / CMN / N.C.
30VDC 2A or 125VAC 0.5A