9
2.0 Performa Cv 962 Control
2.1 Introduction to the Performa CV
Softener and Filter Systems
2.1.1 Performa Cv Softener Valve (278)
The Performa Cv softener valve is available with one of
two controls. The 962 electronic demand system
control and the 962TC electronic time clock control.
The Performa Cv system offers a true 1-inch valve with
superior flow characteristics. The Performa Cv softener
valve will deliver a service flow of 25 gpm (94.6 Lpm) at
a pressure drop of 15 psi (service Cv = 6.5, Kv = 5.6).
The Performa Cv softener is capable of backwashing at
the rate of 20 gpm (75.6 Lpm) with a pressure drop of
25 psi (backwash Cv = 4.0, Kv = 3.5). The application
for this valve will be on softener systems with mineral
tanks up to 21 inches in diameter.
2.1.2 Performa Cv Filter Valve (273)
The Performa Cv filter valve is available with one of
three controls. The 962F electronic demand system
control, the 962FTC electronic time clock control, and
the 942F mechanical time clock control in a 12-day
configuration. The Performa Cv filter valve has the
same service flow capability as the softener valve
however the backwash Cv is higher (Cv = 5.0, Kv = 5.8)
resulting in the capability of backwashing at 25 gpm
(94.6 Lpm) with a 25 psi pressure drop. The Performa
Cv filter valve can be used on carbon filters with media
tank sizes up to 24 inches in diameter. Other filter
media backwash requirements will determine
maximum media tank dimensions. Refer to the
backwash flow requirements in Table 4.5 and Table 4.6.
The Performa Cv softener valve and the Performa Cv
filter valve can be identified by a label attached to the
right side of the valve.
Reynolds Water Conditioning Co.
24545Hathaway
Farmington Hills, MI 48335
800-572-9575